1 1/2" Watts LF288AM2 Atmospheric Vacuum Breaker

Item Number: 0792042
Skip to product information
1 of 1
Regular price $931.50
Special Order
When Will it Ship: Contact for Lead Time
Estimated transit time: 2 to 5 Business Days

Brand - Watts

  • Construction: Lead Free Brass Body
  • Weight: 10.5 lb
  • Orifice: Full size for maximum flow
  • Disc Material: Chemical resistant silicone
  • Primary Function: Prevents backsiphonage
  • Water Compatibility: Hot or cold water
  • Maximum Operating Pressure: 125 PSI
  • Maximum Operating Temperature: 180°F
  • Application: Low flow, non-continuous use

Description

The 1 1/2" Watts LF288AM2 Atmospheric Vacuum Breaker prevents backsiphonage of contaminated water into potable water supplies. Constructed from Lead Free Brass with a chemical-resistant silicone seat disc and a full-size orifice, it ensures maximum flow and minimal pressure loss. This device is suitable for low flow, non-continuous hot or cold water applications like laboratory equipment. It can handle pressures up to 125 PSI and temperatures up to 180°F. This vacuum breaker meets ASSE 1001, ANSI A112.1.1, CSA B64.1.1, and NSF/ANSI 372 standards for reliable performance.

Help Me Connect

Installation Guidelines

  • This atmospheric vacuum breaker (AVB) must be installed a minimum of 6 inches (152mm) above the highest point on the downstream piping.
  • To ensure proper operation, there can be no shutoff valves downstream of this anti-siphon vacuum breaker.

Usage Restrictions

This device is designed for non-continuous pressure applications. It is not recommended for use under continuous pressure or in situations where a backpressure condition may develop. According to ASSE Standard 1001, it must not be subjected to continuous pressure for more than twelve (12) hours.

View full details

Collapsible content

Additional Details

This 1 1/2" Watts Series LF288A Anti-Siphon Vacuum Breaker is designed to prevent the reverse flow of polluted water from entering into the potable water supply due to backsiphonage. It features a full size bore to assure pipe size capacity and maximum flow, making it ideal for low flow, non-continuous hot or cold water health hazard installations such as on laboratory equipment.

Features

  • Constructed with a Lead Free Brass Body and a chemical resistant silicone seat disc.
  • Incorporates an atmospheric vent to prevent spilling under all rates of flow.
  • A full size orifice ensures maximum flow and minimal pressure loss.
  • The durable silicone disc provides high heat and water hammer shock resistance.

Important Safety Notice: This device is not to be used under continuous pressure or where there is a possibility that a backpressure condition may develop. It shall not be subjected to continuous pressure for more than twelve (12) hours per ASSE Std. 1001.

Specifications

  • Body Material: Lead Free Brass
  • Disc Material: Silicone
  • Nominal Size: 1 1/2 inch
  • Connection Type: Female NPT Inlet and Outlet
  • Maximum Operating Temperature: 180°F (82°C)
  • Maximum Working Pressure: 125 PSI (8.6 bar)
  • Orifice: Full Size

Dimensions (Approximate)

  • Dimension A: 3 5/8 inches (92mm)
  • Dimension B: 4 1/2 inches (114mm)
  • Dimension C: 2 1/4 inches (57mm)
  • Dimension D: 2 1/4 inches (57mm)
  • Weight: 54 oz (1531 gm)

Certificates & Approvals

  • ASSE Standard 1001
  • ANSI A112.1.1
  • CSA B64.1.1
  • NSF/ANSI 372
  • UPC

FAQs

What is the primary function of the Watts LF288AM2?

The Watts LF288AM2 is an anti-siphon vacuum breaker designed to prevent the reverse flow (backsiphonage) of polluted water from entering a potable water supply system.

What materials are used in the construction of this vacuum breaker?

It features a Lead Free Brass body and a durable, chemical-resistant silicone seat disc. The lead-free construction ensures compliance with current installation requirements.

What are the recommended installation requirements for the LF288AM2?

This atmospheric vacuum breaker must be installed a minimum of 6 inches above the highest point of the downstream piping. Additionally, there should be no shutoff valves downstream of the device.

Can this device be used under continuous pressure?

No, the LF288AM2 is not designed for continuous pressure applications. It should not be subjected to continuous pressure for more than twelve hours as per ASSE Std. 1001, nor where backpressure conditions may develop.

What types of applications is the LF288AM2 suitable for?

It is ideal for low flow, non-continuous hot or cold water health hazard applications, such as on laboratory equipment, where small amounts of water are used and minimal pressure loss is required.