1 1/4 LF850-QT-FZ DC

Item Number: T683041
Skip to product information
1 of 2
Regular price $1,046.99
Special Order
When Will it Ship: Contact for Lead Time
Estimated transit time: 2 to 5 Business Days

Brand - Febco

  • Valve Size: 1 1/4 inch
  • Body Material: Lead Free* cast copper silicon alloy
  • Maximum Working Pressure: 175 psi
  • Temperature Range: 32°F to 140°F
  • Includes freeze sensor with SentryPlus Alert® technology
  • Compact modular design for easy in-line maintenance
  • NPT ANSI/ASME B1.20.1 end connections
  • Approved by ASSE 1015, NSF/ANSI 61-G, and USC-FCCCHR

Description

This 1 1/4 inch FEBCO LF850 Lead Free Double Check Valve Backflow Preventer Assembly is designed to prevent polluted water from entering the potable water supply in non-health hazard applications. Constructed with Lead Free* cast copper silicon alloy, it features a compact modular design for easy in-line maintenance. It includes a freeze sensor with SentryPlus Alert® technology to alert personnel to freezing conditions, helping protect equipment. With a maximum working pressure of 175 psi and NPT end connections, this assembly is suitable for continuous pressure piping. Approved by ASSE 1015, NSF/ANSI 61-G, and USC-FCCCHR.

Help Me Connect

Connections

  • This backflow preventer features NPT ANSI/ASME B1.20.1 end connections for secure and compliant installation into your piping system.
  • The integral freeze sensor can be activated using an add-on connection kit (sold separately) to enable monitoring and alerts via Wi-Fi networks, Building Management Systems (BMS), or Irrigation Management Systems (IMS).
View full details

Collapsible content

Additional Details

This 1 1/4 inch Lead Free double check valve backflow preventer assembly is designed to prevent the backflow of polluted water from entering the potable water supply due to backsiphonage and or backpressure. It is ideal for protection in continuous pressure piping applications and at cross-connections identified as non-health hazards, such as at the service line entrance.

Its compact modular design facilitates easy maintenance with a single access cover for in-line repairs, ensuring efficient servicing without removing the entire assembly from the line.

Key Features

  • Lead Free* construction to comply with Lead Free installation requirements
  • Compact modular design facilitates maintenance with a single access cover for in-line repairs
  • Two in-line independent positive seating check modules
  • Replaceable seats and seat discs
  • Top-mounted test cocks
  • Quarter turn ball valve shutoffs

Freeze Sensor Technology

  • Includes a freeze sensor for use with SentryPlus Alert® technology to signal facility personnel when temperature nears and reaches the freezing point.
  • The freeze alerts feature is available with an add-on connection kit (sold separately) for Wi-Fi networks, building management systems (BMS), and irrigation management systems (IMS).

WARNING: The freeze sensor solely provides alerts about a possible freeze event and cannot prevent a freeze event from occurring. User action is required to prevent freeze conditions from causing product and/or property damage.

Specifications

  • Valve Size: 1 1/4 inch
  • Body Material: Lead Free* cast copper silicon alloy
  • End Connections: NPT ANSI/ASME B1.20.1
  • Shutoff Type: Quarter Turn Ball Valves
  • Check Modules: Two in-line independent positive seating
  • Elastomer Material: Silicone
  • Spring Material: Stainless Steel
  • Seat Material: Noryl®

Performance Ratings

  • Maximum Working Pressure: 175 psi (12.1 bar)
  • Hydrostatic Test Pressure: 350 psi (24.1 bar)
  • Temperature Range: 32°F to 140°F (0°C to 60°C)

Certifications & Approvals

  • ASSE: 1015
  • IAPMO: UPC
  • NSF/ANSI: 61-G
  • USC-FCCCHR: Approved
  • ANSI/AWWA Conformance: C510-92

FAQs

What is the primary function of the FEBCO LF850 Small Double Check Valve Assembly?

Its primary function is to prevent the backflow of polluted water into the potable water supply due to backsiphonage or backpressure, specifically for non-health hazard applications.

What is "Lead Free" construction?

"Lead Free" construction means that the wetted surface of this product contacted by consumable water contains less than 0.25% of lead by weight, complying with Lead Free installation requirements.

How does the integrated freeze sensor work?

The freeze sensor, part of SentryPlus Alert® technology, monitors temperature and alerts facility personnel when conditions approach or reach freezing. An add-on connection kit (sold separately) is required to activate its full monitoring capabilities with Wi-Fi, BMS, or IMS.

Can the freeze sensor prevent the assembly from freezing?

No, the freeze sensor solely provides alerts about a possible freeze event. It does not prevent freezing itself. User action is required to prevent freeze conditions from causing product and/or property damage.

What type of connections does this backflow preventer use?

This assembly features NPT (National Pipe Taper) ANSI/ASME B1.20.1 end connections for secure and compliant installation into a piping system.