1/2 SS007M3-QT-FZ

Item Number: T062695
Skip to product information
1 of 1
Regular price $2,253.76
Special Order
When Will it Ship: Contact for Lead Time
Estimated transit time: 2 to 5 Business Days

Brand - Watts

  • Nominal Size: 1/2 inch
  • Body Material: Stainless Steel
  • End Connections: NPT
  • Shutoff Valves: Quarter Turn Ball Valves
  • Integrated Freeze Sensor included
  • Replaceable Seats and Discs
  • Maximum Working Pressure: 175 psi
  • Temperature Range: 33°F - 180°F

Description

This Watts Series 007 1/2 inch stainless steel double check valve backflow preventer assembly safeguards drinking water supplies from pollution in non-potable applications like irrigation or industrial processing. It features a durable stainless steel body, NPT end connections, and quarter turn ball valve shutoffs for reliable operation. An integrated freeze sensor, compatible with an optional connection kit for Wi-Fi or BMS alerts, monitors temperature to prevent damage. Its modular design with a single access cover allows for easy in-line maintenance and replaceable internal components. Approved by ASSE, AWWA, IAPMO, and CSA, this assembly ensures compliance and protection against backflow in non-health hazard cross-connections. Item number T062695.

Help Me Connect

Connections

  • This 1/2 inch double check valve backflow preventer assembly features NPT end connections for easy installation into compatible piping systems.
  • The integrated freeze sensor requires an add-on connection kit (sold separately) to activate its communication features with Wi-Fi networks, building management systems (BMS), or irrigation management systems (IMS). Without the kit, the sensor operates passively.

Installation Guidance

Installation must comply with all required instructions, codes, and regulations. Check with the local authority having jurisdiction regarding vertical orientation, frequency of testing, or other specific installation requirements. This assembly is designed for cross-connections identified as non-health hazards.

View full details

Collapsible content

Additional Details

This Watts Series 007 1/2 inch double check valve backflow preventer assembly is designed to protect drinking water supplies from dangerous cross-connections in non-potable service applications such as irrigation, fireline, or industrial processing, in accordance with national plumbing codes and water authority requirements. Its compact modular design allows for easy maintenance with a single access cover for in-line repairs.

Key Features

  • Stainless steel body construction with NPT end connections and quarter turn ball valve shutoffs
  • Includes an integrated freeze sensor for use with SentryPlus Alert® technology to monitor temperature and alert facility personnel when freeze conditions approach or reach freezing.
  • Freeze alerts are available with an add-on connection kit (sold separately) for Wi-Fi networks, building management systems (BMS), and irrigation management systems (IMS).
  • Features two in-line independent positive seating check modules with captured springs and replaceable check discs and seats.
  • Equipped with top mounted ball valve test cocks for easy testing.

A WARNING: The freeze sensor solely provides alerts about a possible freeze event and cannot prevent a freeze event from occurring. User action is required to prevent freeze conditions from causing product and/or property damage. An add-on connection kit (sold separately) is required to activate the freeze sensor's communication features; without it, the sensor is a passive component.

Specifications

  • Nominal Size: 1/2 inch
  • Body Material: Stainless Steel
  • End Connections: NPT
  • Shutoff Valves: Quarter Turn Ball Valves
  • Test Cocks: Top Mounted Ball Valves
  • Check Modules: Two in-line independent positive seating
  • Seat & Disc Material: Replaceable
  • Temperature Range: 33°F - 180°F (0.5°C – 82°C)
  • Maximum Working Pressure: 175 psi (12.1 bar)

Certificates & Approvals

  • ASSE Std. 1015
  • AWWA Std. C510
  • IAPMO PS31
  • CSA B64.5
  • Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California

FAQs

What is the primary function of the Watts Series 007 double check valve assembly?

Its primary function is to protect drinking water supplies from pollution caused by backflow in non-potable service applications such as irrigation, fireline, or industrial processing, in accordance with national plumbing codes.

What type of connections does this backflow preventer use?

This assembly is equipped with NPT end connections, which are standard National Pipe Taper threads, for installation into compatible piping systems.

How does the integrated freeze sensor operate?

The freeze sensor monitors temperature and alerts facility personnel via SentryPlus Alert® technology when temperatures approach or reach freezing conditions. An add-on connection kit (sold separately) is required to enable communication features with Wi-Fi networks, BMS, or IMS.

Is regular maintenance required for this double check valve?

Yes, the compact modular design with a single access cover facilitates easy in-line maintenance. It features replaceable seats and seat discs, and top-mounted ball valve test cocks for periodic testing and servicing.

Does the freeze sensor prevent the product from freezing?

No, the freeze sensor solely provides alerts about a possible freeze event. It does not prevent freezing. User action is required to implement preventative measures and avoid product or property damage from freeze conditions.