1.5 LF860-QT-RP-FS

Item Number: F683004
Skip to product information
1 of 1
Regular price $2,062.22
Limited Stock (5)
Estimated transit time: 2 to 5 Business Days Eligible for Express Shipping

Brand - Febco

  • 1 1/2 inch Lead Free Reduced Pressure Zone Backflow Preventer
  • Max. Working Pressure: 175 psi
  • Temperature Range: 32°F to 140°F
  • Lead Free* Cast Copper Silicon Alloy Body
  • SentryPlus Alert® Flood Sensor for discharge detection
  • Quarter turn ball valves for shutoff
  • Modular relief and check valves for easy maintenance
  • Approved: ASSE 1013, CSA B64.4, NSF 61-G

Description

The 1 1/2 inch FEBCO Series LF860 Small Reduced Pressure Zone Backflow Preventer Assembly provides critical protection against high hazard (toxic) fluid contamination in potable water systems. Featuring Lead Free* cast copper silicon alloy construction and quarter-turn ball valves, it is suitable for industrial, hospital, and irrigation applications. An integrated SentryPlus Alert® flood sensor detects relief valve discharge, relaying signals when connected to an add-on kit for proactive maintenance. It operates up to 175 psi and 140°F, meeting ASSE 1013, CSA B64.4, and NSF 61-G standards.

Help Me Connect

Connections & Compatibility

  • The assembly features NPT ANSI/ASME B1.20.1 end connections for easy installation into existing plumbing systems.
  • The integrated SentryPlus Alert® Flood Sensor requires an add-on connection kit to activate its alert features.
  • Compatible connection kit options include integration with Building Management Systems (BMS), cellular communication, or the Sensor Control Monitor.
  • The Sensor Control Monitor enables connectivity with Building Automation Systems (BAS) via RS-485 Modbus or the Nexa® platform through Wi-Fi.
View full details

Collapsible content

Additional Details

The 1 1/2 inch FEBCO Series LF860 Small Reduced Pressure Zone Backflow Preventer Assembly is engineered to prevent the reverse flow of high hazard (toxic) fluids into potable water systems due to backsiphonage or backpressure conditions.

This assembly is primarily used in health-hazard applications such as industrial plants, hospitals, morgues, mortuaries, chemical plants, irrigation systems, boiler feed, and water lines, and features Lead Free* construction to comply with installation requirements.

Key Features

  • Features Lead Free* cast copper silicon alloy construction for potable drinking water systems.
  • Includes a SentryPlus Alert® Flood Sensor to detect excessive water discharges from the relief valve, providing early notification for corrective action.
  • The assembly contains a lead free bronze body, threaded quarter turn ball valves, top mounted test cocks, spring loaded check valves, and a pressure differential relief valve.
  • Modular relief valve and check valves allow for easy inline maintenance without special tools.
  • Flood alerts can be activated with an add-on sensor connection kit, compatible with BMS, cellular communication, or the Sensor Control Monitor for integration with BAS via RS-485 Modbus or the Nexa® platform through Wi-Fi.

NOTICE: An add-on connection kit is required to activate the flood sensor. Without the connection kit, the sensor is a passive component with no communication with any other device.

Specifications

  • Size: 1 1/2 inch
  • Valve Body Material: Lead Free* Cast Copper Silicon Alloy
  • Elastomers Material: Silicone
  • Springs Material: Stainless steel
  • Max. Working Pressure: 175 psi (12.1 bar)
  • Hydrostatic Test Pressure: 350 psi (24.1 bar)
  • Temperature Range: 32°F to 140°F (0°C to 60°C)
  • End Connections: NPT ANSI/ASME B1.20.1
  • Inlet/Outlet Shutoff: Quarter Turn Ball Valves
  • Flood Detection: SentryPlus Alert® Flood Sensor

Certificates & Approvals

  • ASSE: 1013
  • CSA: B64.4
  • NSF: 61-G
  • ANSI/AWWA Conformance: C511
  • Approved By: Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California

FAQs

What is the primary purpose of the FEBCO LF860 backflow preventer?

The primary purpose is to prevent the reverse flow of high hazard (toxic) fluids into potable drinking water systems, protecting against contamination from backsiphonage or backpressure conditions.

What does "Lead Free* construction" mean for this product?

Lead Free* construction signifies that the wetted surface of the product contacted by consumable water contains less than 0.25% of lead by weight, complying with lead-free installation requirements for potable water systems.

How does the SentryPlus Alert® flood sensor work?

The SentryPlus Alert® flood sensor is integrated into the assembly to detect excessive water discharges from the relief valve. When paired with an add-on connection kit, it activates to relay alerts, notifying personnel for corrective action to prevent flooding and damage.

What types of applications is this backflow preventer suitable for?

This backflow preventer is suitable for various health-hazard applications, including industrial plants, hospitals, morgues, mortuaries, chemical plants, irrigation systems, boiler feed, and general water lines where maximum protection is required.

Are special tools required for maintenance?

No, the FEBCO Series LF860 features an inline serviceable assembly, and its modular relief valve and check valves are designed for easy maintenance, requiring no special tools.