1 LF007M1-QT-FZ

Item Number: T063232
Skip to product information
1 of 1
Regular price $785.27
In Stock (10)
Estimated transit time: 2 to 5 Business Days Eligible for Express Shipping

Brand - Watts

  • Size: 1 inch
  • Body Material: Lead Free* cast copper silicon alloy
  • Connections: NPT end connections
  • Integrated freeze sensor with SentryPlus Alert® technology
  • Shutoffs: Quarter turn ball valves with tee handles
  • Modular, compact design for easy maintenance
  • Maximum Working Pressure: 175 PSI
  • Temperature Range: 33°F - 180°F

Description

This 1 inch Lead Free Double Check Valve Backflow Preventer Assembly, SKU T063232, is designed to prevent the backflow of polluted water into potable water supplies. Ideal for non-health hazard cross-connections and continuous pressure applications, it features a Lead Free* cast copper silicon alloy body and NPT connections. An integrated freeze sensor with SentryPlus Alert® technology provides temperature monitoring and alerts when connected to an add-on kit. Its modular design allows for easy in-line maintenance with replaceable seats and discs. This assembly complies with ASSE 1015, AWWA C510, IAPMO PS31, and CSA B64.5 standards.

Help Me Connect

This 1 inch Lead Free Double Check Valve Backflow Preventer Assembly is designed for easy installation with NPT end connections. Ensure your piping system has matching 1 inch male NPT threads for proper connection.

The integrated freeze sensor is a passive component until activated. To receive temperature alerts, an add-on connection kit (sold separately) is required to enable communication with Wi-Fi networks, building management systems (BMS), or irrigation management systems (IMS).

View full details

Collapsible content

Additional Details

This 1 inch lead free double check valve backflow preventer assembly is designed to prevent the backflow of polluted water from entering into the potable water supply due to backsiphonage or backpressure, in accordance with national plumbing codes and water authority requirements.

Freeze sensor solely provides alerts about a possible freeze event and cannot prevent a freeze event from occurring. User action is required to prevent freeze conditions from causing product and/or property damage.

Design and Construction

  • Features a modular, compact design to facilitate easy in-line maintenance.
  • Constructed with a Lead Free* cast copper silicon alloy body.
  • Includes NPT end connections and quarter turn ball valve shutoffs with tee handles.
  • Equipped with top mounted test cocks.
  • Contains two in-line independent positive seating check modules with captured springs, and replaceable check discs and seats.
  • Applicable iron components are coated with ArmorTek®, a patented three-part advanced epoxy system, to reduce microbial-induced corrosion (MIC) and protect exposed metal substrate.

Freeze Sensor Technology

  • An integrated freeze sensor works with SentryPlus Alert® technology to signal facility personnel when temperature nears and reaches the freezing point.
  • Freeze alerts feature is available with an add-on connection kit (sold separately) for Wi-Fi networks, building management systems (BMS), and irrigation management systems (IMS).
  • The sensor is installed on the assembly exterior and does not alter assembly functions or certifications.

Specifications

  • Size: 1 inch
  • Body Material: Lead Free* cast copper silicon alloy
  • Connection Type: NPT end connections
  • Shutoff Type: Quarter turn ball valves with tee handles
  • Check Modules: Two in-line independent positive seating check modules
  • Test Cocks: Top mounted
  • Coating: ArmorTek powder coating (applied to internal and external surfaces of applicable components)
  • Access Cover Bolts: Stainless steel

Performance

  • Maximum Working Pressure: 175 PSI (12.1 bar)
  • Temperature Range: 33°F – 180°F (0.5°C – 82°C)

Certificates & Approvals

  • ASSE Standard: 1015
  • AWWA Standard: C510
  • IAPMO: PS31
  • CSA: B64.5
  • Additional Approvals: ASSE, AWWA, IAPMO, CSA, UPC, UL Classified (without shutoff valves only), Foundation for Cross-Connection Control and Hydraulic Research at USC

FAQs

What is the primary purpose of this backflow preventer assembly?

This 1 inch Lead Free Double Check Valve Backflow Preventer Assembly is designed to prevent the backflow of polluted water from entering into the potable water supply due to backsiphonage or backpressure.

What does 'Lead Free' mean for this product?

The 'Lead Free' designation indicates that the wetted surface of this product contains less than 0.25% of lead by weight, complying with current Lead Free installation requirements and standards.

How does the integrated freeze sensor function?

The freeze sensor works with SentryPlus Alert® technology to monitor temperature and signal facility personnel about low or freezing conditions. An add-on connection kit (sold separately) is required to activate a monitoring system for Wi-Fi, BMS, or IMS alerts.

What type of connections does this backflow preventer use?

This assembly features 1 inch NPT (National Pipe Taper) end connections, allowing for straightforward installation into compatible piping systems.

Is this backflow preventer easy to maintain?

Yes, its modular, compact design includes a single top-entry cover, facilitating easy in-line maintenance. It also features replaceable seats and seat discs for convenient servicing.