  • Type: Reduced Pressure Zone Backflow Preventer
  • Weight: 14.1 lb
  • Size: 1 inch
  • Body Material: Bronze
  • Maximum Working Pressure: 175 psi
  • Temperature Range: 33°F - 180°F
  • Connections: Union with 360° Elbow Fittings
  • Shutoff Valves: Quarter-turn ball valves with tee handles
  • Special Feature: Integrated SentryPlus Alert® Flood Sensor

Description

This 1 inch Watts U009M2-AQT-FS Reduced Pressure Zone Backflow Preventer Assembly is designed to protect potable water supplies from pollution due to backsiphonage and backpressure, meeting national plumbing codes. Constructed with a durable bronze body, it features union connections and 360-degree elbow fittings for flexible installation. Quarter-turn ball valves ensure reliable shutoff. The compact, modular design allows for easy in-line maintenance. An integrated SentryPlus Alert flood sensor detects excessive water discharge, offering enhanced protection when paired with an add-on connection kit. Maximum working pressure is 175 psi with a temperature range of 33°F to 180°F. Ideal for commercial and industrial applications.

Help Me Connect

Connections

  • This assembly features union connections for easy installation and removal from the piping system.
  • Equipped with elbow fittings that allow for 360 degree rotation, providing flexibility in installation and alignment.
  • The backflow preventer's main purpose is to be installed at the service line to protect potable water supply.
View full details

Collapsible content

Additional Details

This 1 inch reduced pressure zone backflow preventer assembly is designed to prevent the flow of polluted water from entering into the potable water supply due to backsiphonage and or backpressure, in accordance with national plumbing codes and water authority requirements.

Design & Construction

  • Features a compact modular design for easy maintenance with a single access cover for in-line repairs.
  • Constructed with a bronze body for durability.
  • Includes union connections and elbow fittings for 360 degree rotation.
  • Equipped with quarter turn ball valve shutoffs with tee handles and top mounted test cocks.
  • Contains two in-line independent check valves with captured springs and replaceable check seats.
  • An internal relief valve is designed for reduced space requirements.

Flood Detection & Connectivity

  • Integrated flood sensor with SentryPlus Alert® technology detects excessive water discharges from the relief valve.
  • When paired with an add-on connection kit (sold separately), the sensor activates to relay alerts for potential flooding events.
  • Connection kit options include BMS, cellular communication, and the Sensor Control Monitor, enabling integration with BAS via RS‑485 Modbus or the Nexa® platform through Wi-Fi.

Additional Features

  • Unique swivel union for versatile installation.
  • Light body passages provide low pressure drop.
  • No special tools required for servicing internal components.

Specifications

General

  • Body Material: Bronze
  • Discs: Silicone rubber
  • Check Seats: Replaceable polymer
  • Relief Valve Seat: Removable stainless steel
  • Cover Bolts: Stainless steel

Performance

  • Maximum Working Pressure: 175 psi (12 bar)
  • Temperature Range: 33°F - 180°F (0.5°C – 82°C)

Dimensions (1 inch U009M2AQT)

  • Overall Length (A): 13 1/8 inch (333 mm)
  • Height (C): 3 1/8 inch (79 mm)
  • Width (D): 5 1/8 inch (130 mm)
  • Inlet to Outlet Centerline (D1): 5 3/16 inch (132 mm)
  • Connection Radius (R): 2 3/8 inch (60 mm)
  • Weight: 13.88 lb (6.3 kg)

Certificates & Approvals

  • USC Manual 8th Edition
  • ASSE No. 1013
  • AWWA C511
  • CSA B64.4
  • IAPMO File No. 1563
  • Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California

FAQs

What is the primary function of the Watts U009M2-AQT-FS backflow preventer?

The primary function is to prevent polluted water from flowing back into the potable water supply due to backsiphonage or backpressure, ensuring compliance with national plumbing codes.

What materials are used in the construction of this backflow preventer?

This backflow preventer features a bronze body, silicone rubber discs, replaceable polymer check seats, removable stainless steel relief valve seat, and stainless steel cover bolts, ensuring durability.

Does this model include flood detection capabilities?

Yes, it includes an integrated SentryPlus Alert® flood sensor to detect excessive water discharges from the relief valve. An add-on connection kit is required to activate the sensor and relay alerts.

What are the installation benefits of the union connections and elbow fittings?

The union connections allow for easy installation and removal, while the elbow fittings provide 360-degree rotation, offering flexibility in orienting the assembly to fit various piping configurations.

What is the maximum operating pressure and temperature range for this device?

The Watts U009M2-AQT-FS has a maximum working pressure of 175 psi (12 bar) and an operating temperature range of 33°F to 180°F (0.5°C to 82°C).