10 957RPDA-OSY-GPM-FS

Item Number: F111631
Skip to product information
1 of 1
Regular price $27,902.22
Special Order
When Will it Ship: Contact for Lead Time
Estimated transit time: 2 to 5 Business Days

Brand - Watts

  • Nominal Size: 10 inch
  • Weight: 997.0 lb
  • Housing & Sleeve: 304 (Schedule 40) Stainless Steel
  • Shutoff Valves: OSY Resilient Seated Gate Valves
  • Maximum Working Pressure: 175 psi
  • Temperature Range: 33°F - 140°F
  • Includes Flood Sensor with SentryPlus Alert technology
  • Furnished with Gallons Per Minute (GPM) Meter
  • UL Classified and FM Approved

Description

The Watts 957RPDA-OSY-GPM-FS is a 10 inch reduced pressure detector backflow preventer assembly. It is designed to prevent hazardous reverse flow due to backpressure or backsiphonage in horizontal installations. This model features a 304 stainless steel body, UL Classified and FM Approved outside stem and yoke (OSY) resilient seated gate valves, and a gallons per minute meter for leak detection. Key safety features include a flood sensor with SentryPlus Alert technology to detect excessive relief valve discharge. It operates up to 175 psi with a temperature range of 33°F to 140°F.

Help Me Connect

Connections

  • This 10 inch backflow preventer assembly features groove end connections for both the inlet and outlet.
  • The grooved fittings allow for integral pipeline adjustment, simplifying installation into existing piping systems.
View full details

Collapsible content

Additional Details

The Watts 957RPDA-OSY-GPM-FS is a 10 inch reduced pressure detector backflow preventer assembly designed to stop the reverse flow of liquids due to backpressure or backsiphonage where a potential health hazard exists. This assembly is ideal for horizontal installation and is known for its extremely compact and lighter design compared to traditional models.

WARNING: It is illegal to use this product in any plumbing system providing water for human consumption, such as drinking or dishwashing, in the United States. Before installing, consult your local water authority, building and plumbing codes.

Construction & Operation

  • Consists of a 304 (Schedule 40) stainless steel body with a quick access sleeve and groove end connections.
  • Features two independent torsion spring check modules and a differential pressure relief valve located between and below the modules.
  • Includes two drip tight shutoff valves, with UL Classified and FM Approved outside stem and yoke (OSY) resilient seated gate valves.
  • Torsion spring checks utilize reversible elastomer discs for drip tight closure against reverse flow.
  • A gallon per minute meter is furnished on the bypass line to detect underground leaks and unauthorized water use.
  • Includes a bottom mounted cast stainless steel relief valve.

Flood Detection & Monitoring

  • Equipped with a flood sensor with SentryPlus Alert technology to detect excessive water discharges from the relief valve.
  • When paired with an add-on connection kit (sold separately), the sensor can relay alerts for potential flooding events to a Building Automation System (BAS) via RS-485 Modbus or the Nexa platform through Wi-Fi.

Specifications

General

  • Model: 957RPDA
  • Product Type: Reduced Pressure Detector Assembly Backflow Preventer
  • Nominal Size: 10 inch
  • Installation: Horizontal
  • Shutoff Valves: Outside Stem and Yoke (OSY) Resilient Seated Gate Valves
  • Flood Detection: SentryPlus Alert Sensor on Relief Valve
  • Meter: Gallons Per Minute (GPM) Meter

Materials

  • Housing & Sleeve: 304 (Schedule 40) Stainless Steel
  • Elastomers: EPDM, Silicone, Buna 'N'
  • Torsion Spring Checks: Noryl®, Stainless Steel
  • Check Discs: Reversible Silicone or EPDM
  • Test Cocks: Lead Free* Bronze Body
  • Pins & Fasteners: 300 Series Stainless Steel
  • Springs: Stainless Steel
  • Relief Valve: Cast Stainless Steel (bottom mounted)

Pressure & Temperature

  • Maximum Working Pressure: 175 psi (12.1 bar)
  • Temperature Range: 33°F - 140°F (0.5°C - 60°C)

Certificates & Approvals

  • Approved by Foundation for Cross-Connection Control and Hydraulic Research (FCCCHR-USC)
  • AWWA C511-97
  • ASSE 1047
  • CSA B64.4
  • UL Classified (OSY Only)
  • FM Approved (OSY Only)

FAQs

What is the primary function of the Watts 957RPDA-OSY-GPM-FS backflow preventer?

Its primary function is to prevent the reverse flow of non-potable liquids into the potable water supply due to backpressure or backsiphonage, particularly in situations where a potential health hazard exists.

What type of shutoff valves are included with this assembly?

This assembly is equipped with UL Classified and FM Approved 10-inch outside stem and yoke (OSY) resilient seated gate valves for reliable shutoff.

Does this backflow preventer have flood detection capabilities?

Yes, it includes a flood sensor with SentryPlus Alert technology on the relief valve to detect continuous or excessive water discharges, signaling potential issues.

What material is the housing and sleeve constructed from?

The housing and sleeve are constructed from durable 304 (Schedule 40) stainless steel pipe, providing robust protection and longevity.

What are the working pressure and temperature limits for this device?

This backflow preventer has a maximum working pressure of 175 psi (12.1 bar) and can operate within a temperature range of 33°F to 140°F (0.5°C to 60°C).