Brand - Ames

  • Product Type: Double Check Valve Backflow Preventer Assembly
  • Weight: 1091.0 lb
  • Size: 10 inch
  • Model: Maxim M200N
  • Shutoff Valves: Non-Rising Stem (NRS)
  • Housing Material: 304 (Schedule 40) Stainless Steel
  • Maximum Working Pressure: 175 PSI
  • Lead Content: Wetted surface contains less than 0.25% lead by weight
  • Key Approvals: ASSE 1015, AWWA C510-97, NSF/ANSI 61-G

Description

This Maxim M200N 10 inch lead free double check valve backflow preventer assembly prevents non-potable water and fire protection substances from contaminating the potable water supply due to backpressure or backsiphonage. Designed for non-health hazard cross-connections, it features a durable 304 stainless steel housing, two independent Tri-Link Checks for lowest pressure loss, and non-rising stem (NRS) shutoff valves. Its compact, modular design with a single access sleeve allows for easy maintenance without special tools. Approved for horizontal, vertical, and N pattern installations, this assembly has a maximum working pressure of 175 PSI and is certified ASSE 1015, AWWA C510-97, and NSF/ANSI 61-G.

Help Me Connect

Connections

  • This double check valve assembly is designed with groove end connections for integral pipeline adjustment.
  • It can be installed in Horizontal, Vertical, or N Pattern configurations to suit various piping layouts.
View full details

Collapsible content

Additional Details

This Maxim 10 inch lead free double check valve backflow preventer assembly is designed to prevent the reverse flow of fire protection substances and water of non-potable quality from being pumped or siphoned into the potable water supply due to backsiphonage and/or backpressure in accordance with national plumbing codes and water authority requirements. It is ideal for protection at cross-connections identified as non-health hazards, such as on high flow fire systems and from other contaminants found at the service line entrance, for use in non-health hazard applications.

The assembly consists of two independently operating check valves, two non-rising stem (NRS) shutoff valves, and four test cocks.

Key Features

  • Extremely Compact Design that is 70% lighter than traditional designs
  • Housing and sleeve constructed of 304 (Schedule 40) stainless steel pipe with groove end connections
  • Patented Tri-Link Checks provide lowest pressure loss and drip tight closure against reverse flow
  • Checks are removable and serviceable without special tools
  • Features a single housing sleeve access port design for easy maintenance and unmatched ease of serviceability
  • Equipped with reversible EPDM or Silicone elastomer check discs
  • Includes Lead Free* Bronze Body test cocks
  • Groove fittings allow integral pipeline adjustment
  • Approved for Horizontal, Vertical, or N Pattern Installations

*The wetted surface of this product contacted by consumable water contains less than 0.25% of lead by weight.

Specifications

General

  • Product Type: Double Check Valve Backflow Preventer Assembly
  • Brand: Maxim
  • Model: M200N
  • Size: 10 inch
  • Shutoff Valves: Non-Rising Stem (NRS) Resilient Seated Gate Valves
  • Check Valves: Tri-Link Checks
  • Installation Patterns: Horizontal, Vertical, N Pattern
  • Maximum Working Pressure: 175 PSI (12.06 bar)
  • Temperature Range: 33°F - 110°F (0.5°C – 43°C)
  • Lead Content: Wetted surface contains less than 0.25% lead by weight

Materials

  • Housing & Sleeve: 304 (Schedule 40) Stainless Steel
  • Elastomers: EPDM, Silicone, Buna 'N'
  • Tri-Link Checks: Noryl®, Stainless Steel
  • Check Discs: Reversible Silicone or EPDM
  • Test Cocks: Lead Free* Bronze Body
  • Pins & Fasteners: 300 Series Stainless Steel
  • Springs: Stainless Steel

Dimensions & Weight (10 Inch NRS)

  • Overall Length: 45 3/4 inches (1162 mm)
  • Weight: 890 lbs (404 kg)

Certificates & Approvals

  • Approved by the Foundation for Cross-Connection Control and Hydraulic Research at The University of Southern California (FCCCHR-USC)
  • AWWA C510-97
  • ASSE 1015
  • NSF Certified to NSF/ANSI 61-G

FAQs

What is the primary use of the Maxim M200N Double Check Valve Assembly?

It is designed to prevent the backflow of non-potable water and fire protection substances into the potable water supply system, especially in non-health hazard applications and on high flow fire systems.

What are the key components of this backflow preventer?

The assembly consists of two independently operating Tri-Link check valves, two non-rising stem (NRS) shutoff valves, and four test cocks.

What material is the housing and sleeve made from?

The housing and sleeve are constructed from durable 304 (Schedule 40) stainless steel pipe with groove end connections.

Is this product suitable for potable water applications concerning lead content?

Yes, the wetted surface of this product that comes into contact with consumable water contains less than 0.25% of lead by weight, making it lead-free. It is NSF Certified to NSF/ANSI 61-G.

What are the maximum operating pressure and temperature limits for this assembly?

This backflow preventer has a maximum working pressure of 175 PSI (12.06 bar) and operates within a temperature range of 33°F to 110°F (0.5°C to 43°C).