Brand - Ames

  • Size: 2 1/2 inch
  • Weight: 176.0 lb
  • Lead Free Reduced Pressure Zone Backflow Preventer
  • Flood sensor with SentryPlus Alert® technology
  • Approved for Horizontal Z-pattern installation
  • Housing Material: Type 304 (Schedule 40) Stainless Steel
  • Shutoff Valves: Non-Rising Stem (NRS)
  • Maximum Working Pressure: 175 psi
  • Certifications: AWWA C511-97, ASSE 1013, CSA B64.4, NSF/ANSI 61-G

Description

The Ames Fire & Waterworks Colt Series C400 2 1/2 inch Reduced Pressure Zone backflow preventer is a lead-free assembly designed for health hazard applications, preventing contamination from backsiphonage and backpressure in potable water systems. It features a Type 304 stainless steel body, non-rising stem gate valves, and a flood sensor with SentryPlus Alert® technology to detect excessive relief valve discharge. This compact unit is approved for horizontal Z-pattern installation and is certified to AWWA C511-97, ASSE 1013, CSA B64.4, and NSF/ANSI 61-G, offering reliable protection with easy serviceability. Item number F0191300.

Help Me Connect

This Colt Series C400 backflow preventer is designed for installation in horizontal Z-pattern configurations. It features groove fittings for integral pipeline adjustment and easy installation. An add-on connection kit (sold separately) is required to activate the flood sensor's alert capabilities, enabling integration with systems like BAS via RS-485 Modbus or the Nexa® platform through Wi-Fi, or cellular communication.

View full details

Collapsible content

Additional Details

This Colt™ 2 1/2 inch lead free reduced pressure zone backflow preventer assembly is designed to prevent the reverse flow of fire protection substances and water of non-potable quality from being pumped or siphoned into the potable water supply due to backsiphonage and/or backpressure. It is approved for horizontal Z pattern installation and is ideal for protection in continuous pressure piping applications and at cross-connections identified as health hazards.

Features

  • Includes a flood sensor with SentryPlus Alert® technology to detect excessive water discharges from the relief valve.
  • When paired with an add-on connection kit (sold separately), the sensor activates to relay alerts for potential flooding events.
  • Extremely compact design, up to 70% lighter than traditional designs.
  • Constructed with a Type 304 (Schedule 40) stainless steel housing and sleeve for durability.
  • Features groove fittings for integral pipeline adjustment and unmatched ease of serviceability.
  • Incorporates a patented link check for lowest pressure loss and reversible silicone or EPDM check disc rubber.
  • Equipped with drip tight shutoff valves and non-rising stem (NRS) resilient seated gate valves.

Installation must be done by a trained product installer, and all required instructions, codes, and regulations related to installation, operation, and maintenance must be followed. Proper drainage must be provided for any discharge. The flood sensor does not replace these requirements.

Specifications

General

  • Size: 2 1/2 inch
  • Pattern: Z-Pattern Horizontal
  • Lead Free: Yes (Wetted surface contains less than 0.25% lead)
  • Flood Sensor: Included, SentryPlus Alert® technology
  • Shutoff Type: Non-Rising Stem (NRS) Resilient Seated Gate Valves

Materials

  • Housing & Sleeve: Type 304 (Schedule 40) Stainless Steel
  • Elastomers: EPDM, Silicone, Buna 'N'
  • Link Checks: Noryl®, Stainless Steel
  • Check Discs: Reversible Silicone or EPDM
  • Test Cocks: Lead Free Bronze Body
  • Pins & Fasteners: 300 Series Stainless Steel
  • Springs: Stainless Steel

Performance

  • Temperature Range: 33°F - 140°F (0.5°C - 60°C)
  • Maximum Working Pressure: 175 psi (12.1 bar)

Certificates & Approvals

  • AWWA C511-97
  • ASSE 1013
  • CSA B64.4
  • NSF Certified to NSF/ANSI 61-G
  • Foundation for Cross-Connection Control and Hydraulic Research at The University of Southern California (FCCCHR-USC)

Dimensions & Weight (approximate)

  • Length (A): 30 3/4 inch (781 mm)
  • Height (C, NRS): 16 3/8 inch (416 mm)
  • Width (D): 9 3/8 inch (238 mm)
  • Weight: 126 lb (57 kg)

FAQs

What is the primary purpose of the Colt Series C400 backflow preventer?

The primary purpose is to protect potable water systems from contamination due to backsiphonage and backpressure, making it suitable for health hazard applications in fire protection and continuous pressure piping.

Does this backflow preventer include a flood sensor?

Yes, it includes a flood sensor with SentryPlus Alert® technology to detect excessive water discharge from the relief valve. An add-on connection kit (sold separately) is needed to activate the alert functionality.

What type of shutoff valves does this model use?

This specific model, the C400Z-NRS-FS, uses Non-Rising Stem (NRS) resilient seated gate valves.

What are the key material components of this assembly?

The housing and sleeve are made from Type 304 (Schedule 40) stainless steel, with elastomers of EPDM, silicone, and Buna 'N'. Test cocks are lead-free bronze.

What installation configurations are supported for this backflow preventer?

This backflow preventer is approved for horizontal Z-pattern installation, and is also configurable for horizontal and N-pattern installations.