3 4000SS-NRS-FS
Item Number: F0690488Brand - Ames
Couldn't load pickup availability
- Size: 3 inch
- Weight: 255.0 lb
- Body Material: 300 Series Stainless Steel
- Shutoff Valves: Non-Rising Stem (NRS)
- Flood Sensor: SentryPlus Alert® Technology Included
- Maximum Working Pressure: 175 psi
- Temperature Range: 33°F - 110°F
- Lightweight stainless steel body
- Short end-to-end dimensions for easy retrofitting
Description
Description
Help Me Connect
Help Me Connect
Flood Sensor Connectivity
The integrated flood sensor requires an add-on connection kit for activation and communication. Compatible connection kit options include those for BMS (Building Management Systems), cellular network communication, or the Sensor Control Monitor.
- The Sensor Control Monitor enables integration with BAS (Building Automation Systems) via RS-485 Modbus.
- Alternatively, the Sensor Control Monitor can integrate with the Nexa® platform through Wi-Fi connectivity for remote alerts.

Collapsible content
Additional Details
This 3 inch Lead Free Reduced Pressure Zone Backflow Preventer Assembly is designed to prevent the reverse flow of fire protection substances and non-potable water into the potable water supply due to backsiphonage and backpressure.
It is ideal for protection in continuous pressure piping applications and at cross-connections identified as health hazards and from other contaminants found at the service line entrance.
Construction & Design
- Features a short lay length, lightweight stainless steel body for reduced installation and shipping costs.
- Equipped with resilient seated shutoff valves with non-rising stem (NRS).
- The cam-check assembly provides maximum flow at low pressure drop.
- Utilizes a stainless steel relief valve with a balanced rolling diaphragm to eliminate sliding seals and lower maintenance costs.
- Compact modular design facilitates easy maintenance with a single access cover for in-line repairs.
- Internal metal parts are 300 Series stainless steel for corrosion resistance.
- Check assembly is made of Noryl®.
Flood Sensor Technology
- Includes a flood sensor with SentryPlus Alert® technology to detect excessive water discharges from the relief valve.
- When paired with an add-on connection kit, the sensor activates to relay alerts for potential flooding events.
- Connection kit options include BMS, cellular communication, and the Sensor Control Monitor which enables integration with BAS via RS-485 Modbus or the Nexa® platform through Wi-Fi.
- An add-on connection kit is required to activate the flood sensor. Without the connection kit, the flood sensor is a passive component that has no communication with any other device.
Specifications
- Size: 3 inch
- Body Material: 300 Series Stainless Steel
- Internal Metal Parts: 300 Series Stainless Steel
- Check Assembly Material: Noryl®
- Shutoff Valves: Non-Rising Stem (NRS)
- Flood Sensor: Included, SentryPlus Alert® Technology
- Temperature Range: 33°F - 110°F (0.5°C – 43°C)
- Maximum Working Pressure: 175 psi (12.1 bar)
- Lay Length: Short
Certificates & Approvals
- AWWA Standard: AWWA C511-92
- ASSE Standard: ASSE 1013
- CSA Standard: CSA B64.5