3 C400Z-BFG-FS
Item Number: F0191481
1
/
of
1
Regular price
$8,277.75
Special Order
When Will it Ship:
Contact for Lead Time
Estimated transit time: 2 to 5 Business Days
Brand - Ames
Couldn't load pickup availability
- Size: 3 inch
- Weight: 93.0 lb
- Lead Free Construction (<0.25% lead)
- Housing Material: Type 304 (Schedule 40) stainless steel
- Flood Sensor: SentryPlus Alert® technology for discharge detection
- Valve Type: Grooved gear operated butterfly with tamper switch
- Maximum Operating Pressure: 175 PSI
- Temperature Range: 33°F - 140°F
- Installation Configuration: Horizontal Z pattern
Description
Description
The Colt 3 inch Lead Free Reduced Pressure Zone (RPZ) backflow preventer assembly is designed to protect potable water systems from contamination due to backsiphonage or backpressure. This Z pattern horizontal unit is ideal for health hazard applications and continuous pressure piping. It features a durable Type 304 stainless steel body, grooved gear operated butterfly valves with tamper switch, and a flood sensor with SentryPlus Alert® technology for detecting relief valve discharges. Approved by ASSE 1013, CSA B64.4, UL, FM, and NSF/ANSI 61-G, ensuring compliance and reliable performance.
Help Me Connect
Help Me Connect
Installation & Connections
- This assembly is approved for horizontal Z pattern installation. Ensure the backflow assembly is installed in accordance with the direction of the flow arrow.
- Features groove couplings for straightforward installation and easy pipeline alignment with compatible piping.
- An add-on connection kit (sold separately) is required to activate the integrated flood sensor's alert capabilities.
- With the connection kit, the sensor can integrate with Building Automation Systems (BAS) via RS‑485 Modbus or the Nexa® platform through Wi-Fi, and also supports BMS or cellular communication.

Collapsible content
Additional Details
This Colt 3 inch lead free reduced pressure zone backflow preventer assembly prevents the reverse flow of fire protection substances and non-potable water from entering the potable water supply due to backsiphonage or backpressure. It is approved for horizontal Z pattern installation in health hazard applications and continuous pressure piping applications.
Flood Detection & Alerting
- Features a flood sensor with SentryPlus Alert® technology to detect continuous discharge from the relief valve.
- An add-on sensor connection kit is required to activate the flood sensor and relay alerts; without it, the sensor is passive.
- Connection kit options include BMS, cellular communication, and the Sensor Control Monitor for integration with BAS via RS‑485 Modbus or the Nexa® platform through Wi-Fi.
Construction & Design
- Constructed with a Type 304 (Schedule 40) stainless steel housing and sleeve, ensuring durability.
- Designed with an extremely compact form factor, making it approximately 70% lighter than traditional designs.
- Includes torsion spring link check modules for unmatched ease of serviceability and lowest pressure loss.
- Features grooved gear operated butterfly valves with tamper switch for reliable shutoff.
- Equipped with a quick access sleeve, test cocks, and a bottom mounted pressure relief valve.
- Replaceable check disc rubber and drip tight shutoff valves ensure dependable performance.
- Groove couplings allow for easy installation and pipeline adjustment.
Specifications
- Size: 3 inch
- Model: C400Z-BFG-FS
- Configuration: Z pattern horizontal
- Housing & Sleeve Material: Type 304 (Schedule 40) stainless steel
- Elastomer Materials: EPDM, Silicone, Buna 'N'
- Link Check Materials: Noryl®, Stainless steel
- Check Discs: Reversible silicone or EPDM
- Test Cock Material: Lead Free* bronze body
- Pins & Fastener Material: 300 Series stainless steel
- Spring Material: Stainless steel
- Valve Type: Grooved gear operated butterfly valves with tamper switch
- Flood Sensor: Included, SentryPlus Alert® technology
- Temperature Range: 33°F - 140°F (0.5°C ~ 60°C)
- Maximum Working Pressure: 175 psi (12.1 bar)
- Lead Content: Wetted surface contains less than 0.25% of lead by weight
Certificates & Approvals
- Approved by Foundation for Cross-Connection Control and Hydraulic Research at The University of Southern California (FCCCHR-USC)
- AWWA C511-97
- ASSE 1013
- CSA B64.4
- UL Classified (BFG & OSY Only)
- FM Approved (BFG & OSY Only)
- NSF/ANSI 61-G Certified
FAQs
What is the primary function of this backflow preventer?
This Colt 3 inch Lead Free Reduced Pressure Zone assembly is designed to prevent the reverse flow of contaminated non-potable water or substances into the potable water supply, protecting against backsiphonage and backpressure.
Does this backflow preventer come with a flood sensor?
Yes, it includes a flood sensor with SentryPlus Alert® technology to detect excessive water discharges from the relief valve. An add-on connection kit is required to activate its alert capabilities.
What type of installation is this model designed for?
This assembly is approved for horizontal Z pattern installation. It is important to install it in accordance with the direction of the flow arrow and local codes.
What materials are used for the main body components?
The housing and sleeve are constructed from Type 304 (Schedule 40) stainless steel. Other components include EPDM, silicone, and Buna 'N' elastomers, Noryl® link checks, and Lead Free* bronze test cocks.
What are the maximum operating pressure and temperature limits?
This backflow preventer has a maximum working pressure of 175 psi (12.1 bar) and an operating temperature range of 33°F to 140°F (0.5°C to 60°C).