6 7001-1-Clean Out-Groove x Groove
Item Number: 0690975Brand - Ames
Couldn't load pickup availability
- Nominal Pipe Size: 6 inch (150mm)
- Weight: 261.0 lb
- Body Material: Epoxy coated steel
- Connections: Grooved (Groove x Groove)
- Cleanout Port: 1
- Maximum Working Pressure: 175 PSI
- Maximum Water Temperature: 140°F
- Screen Material: 304 Stainless Steel with .25" perforation
- CULUS Listed 321, FM Approved Class 5551
Description
Description
Help Me Connect
Help Me Connect
This 6 inch Ames Fire & Waterworks Series 7001 strainer features grooved connections on both ends, designed to connect to compatible grooved piping systems. The grooved ends conform to AWWA C606 standards, ensuring secure and reliable integration into your fire protection water spray system.

Collapsible content
Additional Details
This 6 inch Ames Fire & Waterworks Series 7001 fire service strainer is designed for use in non-potable water spray systems to protect against clogging from large particles, specifically those 1/4 inch diameter or larger, that could foul sprinkler heads and other devices.
Features
- Epoxy coated fabricated steel strainer body
- Grooved connections (groove x groove)
- Single cleanout port
- Large solids trap to minimize screen blockage
- 304 stainless steel strainer element with .25 diameter perforation
- Filter designed for removal and replacement without removing the body from the line
▲ WARNING: It is illegal to use this product in any plumbing system providing water for human consumption, such as drinking or dishwashing, in the United States. Before installing standard material product, consult your local water authority, building and plumbing codes.
Specifications
- Nominal Pipe Size: 6 inch (150mm)
- Body & Cover Material: Fusion-bonded epoxy coated steel
- Screen Material: 304 stainless steel
- Screen Perforation: .25 diameter
- Clean-Out Plug Material: Brass or Bronze
- Connections: Grooved
- Groove Standard: AWWA C606
- Maximum Working Pressure: 175 PSI (12.1 bar)
- Maximum Water Temperature: 140°F (60°C)
- Plugged Filter Withstand Pressure: 125 PSI (8.6 bar)
- Clean Filter Friction Loss: Not to exceed 3 PSI (21 kPa)
- Foreign Material Friction Loss: Not to exceed 10 PSI (69 kPa)
- Open Screen Area: At least 6 times nominal pipe size open area
Certificates & Approvals
- CULUS Listed 321
- FM Approved Class 5551