6 C400-OSY-FxG-FS

Item Number: F0191571
Skip to product information
1 of 1
Regular price $13,329.75
Special Order
When Will it Ship: Contact for Lead Time
Estimated transit time: 2 to 5 Business Days

Brand - Ames

  • Product Type: Reduced Pressure Zone Backflow Preventer
  • Weight: 410.0 lb
  • Nominal Size: 6 inch
  • Connection Type: Flanged Inlet x Grooved Outlet
  • Housing Material: Type 304 (Schedule 40) Stainless Steel
  • Maximum Working Pressure: 175 psi
  • Flood Sensor: Integrated with SentryPlus Alert® technology
  • Lead Content: Wetted surface less than 0.25% lead by weight
  • Installation: Horizontal, Z-pattern, N-pattern

Description

This 6-inch Ames C400 Lead Free Reduced Pressure Zone Backflow Preventer protects potable water systems from contamination by backsiphonage or backpressure. Ideal for fire protection and health hazard applications, it features a durable Type 304 stainless steel housing and sleeve, with OSY resilient seated gate valves. The flanged inlet and grooved outlet connections provide easy installation. An integrated flood sensor with SentryPlus Alert® technology detects excessive relief valve discharge, offering notification capabilities when paired with an add-on connection kit. Approved by AWWA, ASSE, UL, FM, and NSF, ensuring reliable performance and compliance for continuous pressure piping.

Help Me Connect

Connections

  • This backflow preventer features a flanged inlet connection for secure attachment to a corresponding flanged pipe.
  • The grooved outlet connection is designed for easy installation and alignment with grooved piping systems, offering flexibility in pipe adjustments.
  • The assembly is compatible with OSY (Outside Stem and Yoke) resilient seated gate valves, including an option for an integrated supervisory switch.

Flood Sensor Activation

  • The integrated flood sensor with SentryPlus Alert® technology requires an add-on connection kit for activation of communication features and relaying alerts for potential flooding events.
  • Connection kits are available for BMS, cellular communication, or the Sensor Control Monitor for integration with BAS via RS-485 Modbus or the Nexa® platform via Wi-Fi.
View full details

Collapsible content

Additional Details

This Colt™ 6 inch reduced pressure zone backflow preventer assembly is designed to protect potable water systems from contamination by preventing the reverse flow of non-potable substances due to backsiphonage or backpressure. It is suitable for continuous pressure piping applications and cross-connections identified as health hazards.

Construction & Design

  • Features a durable Type 304 (Schedule 40) stainless steel housing and sleeve.
  • Includes two independent torsion spring Link Check modules for ease of serviceability and lowest pressure loss.
  • Equipped with OSY (Outside Stem and Yoke) resilient seated gate valves with a flanged inlet and grooved outlet connection.
  • Designed for horizontal installation, also configurable for "Z" pattern and "N" pattern horizontal installations.
  • Features an extremely compact design, making it approximately 70% lighter than traditional designs.

Flood Sensor Technology

  • Integrated flood sensor with SentryPlus Alert® technology detects excessive water discharges from the relief valve.
  • When paired with an add-on connection kit, the sensor activates to relay alerts for potential flooding events.
  • Connection kit options include BMS, cellular communication, or the Sensor Control Monitor for integration with BAS via RS-485 Modbus or the Nexa® platform via Wi-Fi.
  • Includes an integrated supervisory switch as an option on each gate valve of the OS&Y model.

An add-on connection kit is required to activate the flood sensor's communication features; without it, the sensor is passive.

Specifications

  • Product Type: Reduced Pressure Zone Backflow Preventer
  • Series: C400
  • Nominal Size: 6 inch
  • Connection Type: Flanged Inlet x Grooved Outlet
  • Valve Type: OSY Resilient Seated Gate Valves
  • Housing & Sleeve Material: Type 304 (Schedule 40) Stainless Steel
  • Elastomers: EPDM, Silicone, Buna 'N'
  • Link Check Material: Noryl®, Stainless Steel
  • Check Disc Material: Reversible Silicone or EPDM
  • Test Cock Material: Lead Free* Bronze Body
  • Pins & Fasteners Material: 300 Series Stainless Steel
  • Spring Material: Stainless Steel
  • Temperature Range: 33°F - 140°F (0.5°C - 60°C)
  • Maximum Working Pressure: 175 psi (12.1 bar)
  • Lead Content: Wetted surface contains less than 0.25% of lead by weight
  • Installation Configuration: Horizontal, "Z" pattern horizontal, "N" pattern horizontal

Dimensions (Approximate)

  • Overall Length (A): 43 1/2 in (1105 mm)
  • Height (C OSY): 30 1/8 in (765 mm)
  • Width (D): 16 in (406 mm)
  • Valve Centerline to Valve Centerline (G): 8 1/2 in (216 mm)
  • Inlet to Outlet (H): 44 3/4 in (1137 mm)
  • Relief Valve to Ground (J): 35 1/4 in (895 mm)
  • Valve Body Width (M): 23 3/16 in (589 mm)
  • Drain Height (P): 13 1/16 in (332 mm)

Weight

  • Approximate Weight (OSY): 339 lb (154 kg)

Certificates & Approvals

  • Approved by Foundation for Cross-Connection Control and Hydraulic Research at The University of Southern California (FCCCHR-USC)
  • AWWA C511-97
  • ASSE 1013
  • CSA B64.4
  • UL Classified (OSY)
  • FM Approved (OSY)
  • NSF Certified to NSF/ANSI 61-G

FAQs

What is the primary purpose of this Ames C400 backflow preventer?

This backflow preventer is designed to protect potable water systems from contamination by preventing the reverse flow of non-potable substances caused by backsiphonage or backpressure, particularly in fire protection and health hazard applications.

What type of connections does this 6-inch backflow preventer have?

This model features a flanged inlet gate connection and a grooved outlet gate connection, designed for secure and flexible installation with compatible piping systems.

How does the integrated flood sensor work?

The flood sensor with SentryPlus Alert® technology detects excessive water discharges from the relief valve. To activate its communication features and relay alerts (via BMS, cellular, or Wi-Fi), an add-on connection kit is required.

What are the main materials used in the construction of this assembly?

The housing and sleeve are made from durable Type 304 (Schedule 40) stainless steel. Elastomers include EPDM, silicone, and Buna 'N', while link checks are Noryl® and stainless steel. Test cocks are Lead Free* bronze.

What are the approved installation configurations for this backflow preventer?

This assembly is approved for horizontal installation. It is also configurable for "Z" pattern horizontal and "N" pattern horizontal installations, provided it's installed according to the direction of flow.