- Nominal Size: 6 inch
- Weight: 285.0 lb
- Assembly Type: Reduced Pressure Detector Backflow Preventer
- Housing Material: 304 (Schedule 40) Stainless Steel
- Shutoff Valves: Grooved Gear Operated Butterfly with Tamper Switch
- Connections: Grooved Inlet and Outlet
- Flood Detection: SentryPlus Alert® Technology Flood Sensor
- Maximum Working Pressure: 175 PSI
- Approved for Horizontal N Pattern Installation
Description
Description
Help Me Connect
Help Me Connect
Connections
- This assembly features grooved inlet and outlet connections for straightforward pipe alignment and installation.
Flood Sensor Activation
The integrated flood sensor requires an add-on connection kit to become active and relay alerts for potential flooding events. Connection kit options allow for integration with various systems:
- Building Management Systems (BMS)
- Cellular communication
- Sensor Control Monitor for integration with Building Automation Systems (BAS) via RS‑485 Modbus or the Nexa® platform through Wi‑Fi.

Collapsible content
Additional Details
This Colt™ 6 inch reduced pressure detector backflow preventer assembly is designed to prevent the reverse flow of fire protection substances and water of non-potable quality from being pumped or siphoned into the potable water supply due to backsiphonage and or backpressure.
This compact modular design is approved for horizontal N pattern installation. It consists of a stainless steel body with a quick access sleeve, torsion spring check valves, grooved gear operated butterfly valves with tamper switch, test cocks, and a corrosive resistant bottom mounted pressure relief valve. It comes furnished with a gallon per minute meter to detect underground leaks and unauthorized water use. This backflow assembly contains a flood sensor with SentryPlus Alert® technology to detect excessive water discharges from the relief valve. When paired with an add‑on connection kit, the sensor is activated to relay alerts for potential flooding events. Connection kit options include BMS, cellular communication, and the Sensor Control Monitor which enables integration with BAS via RS‑485 Modbus or the Nexa® platform through Wi‑Fi.
A WARNING: It is illegal to use this product in a plumbing system providing water for human consumption, such as drinking or dishwashing, in the United States. Before installing standard material product, consult your local water authority, building and plumbing codes.
Specifications
- Assembly Type: Reduced Pressure Detector Backflow Preventer
- Nominal Size: 6 inch
- Configuration: Horizontal N pattern
- Housing & Sleeve Material: 304 (Schedule 40) Stainless Steel
- Shutoff Valves: Grooved Gear Operated Butterfly Valves with Tamper Switch
- Inlet Connection: Grooved
- Outlet Connection: Grooved
- Detector: Gallon Per Minute Meter
- Relief Valve: Bottom Mounted Cast Stainless Steel
- Test Cocks: Lead Free* Bronze Body, Nickel Plated
- Elastomers: EPDM, Silicone, Buna 'N'
- Link Checks: Noryl®, Stainless Steel
- Check Discs: Reversible Silicone or EPDM
- Pins & Fasteners: 300 Series Stainless Steel
- Springs: Stainless Steel
- Flood Sensor: Yes, with SentryPlus Alert® Technology
- Temperature Range: 33°F - 140°F (0.5°C ~ 60°C)
- Maximum Working Pressure: 175 PSI (12.1 bar)
Certificates & Approvals
- Approved by Foundation for Cross-Connection Control and Hydraulic Research at The University of Southern California (FCCCHR-USC)
- AWWA C511-97
- ASSE 1047
- CSA B64.4
- UL Classified (BFG)
- FM Approved (BFG)
FAQs
What is the primary function of the Colt C500N-BFG-G-FS assembly?
What material is used for the main housing of this backflow preventer?
Does this model include a flood sensor, and how does it work?
What type of shutoff valves are installed on this 6-inch assembly?
What are the connection types for the inlet and outlet of this backflow preventer?
Related Products
-
Item Number: 7019628
Ames® 2 1/2" –10" 400/500 Lead Free Air Gap Drain Fitting w/ Splash Guard
Regular price $253.88Limited Stock