8 957RPDA-DOSY-CFM-FS
Item Number: F113101Brand - Watts
Couldn't load pickup availability
- Reduced Pressure Detector Assembly, 8 inch
- Weight: 610.0 lb
- Protects potable water systems from contamination
- 304 (Schedule 40) stainless steel housing and sleeve
- Flood sensor with SentryPlus Alert technology included
- UL Classified and FM Approved
- Maximum Working Pressure: 175 psi
- Temperature Range: 33°F – 140°F
- Metered bypass for leak and theft detection
Description
Description
Help Me Connect
Help Me Connect
Connections and Connectivity
- This 8 inch reduced pressure detector assembly features groove fittings, allowing for integral pipeline adjustment and flexible installation.
- The included flood sensor requires an add-on connection kit (sold separately) for activation, enabling communication with Building Management Systems (BMS), cellular networks, or integration with Building Automation Systems (BAS) via RS-485 Modbus or the Nexa platform through Wi-Fi.

Collapsible content
Additional Details
This 8 inch reduced pressure detector backflow preventer assembly prevents the reverse flow of liquids due to backpressure or backsiphonage, protecting potable water systems from contamination where a potential health hazard exists.
It is designed for health hazard applications and includes a flood sensor with SentryPlus Alert technology to detect excessive water discharges from the relief valve.
A WARNING: It is illegal to use this product in any plumbing system providing water for human consumption, such as drinking or dishwashing, in the United States. Before installing standard material product, consult your local water authority, building and plumbing codes.
Key Features
- Provides protection to the potable water system from contamination in accordance with national plumbing codes.
- Extremely compact design and 70% lighter than traditional designs for smaller enclosures.
- Constructed with a 304 (Schedule 40) stainless steel housing and sleeve.
- Groove fittings allow integral pipeline adjustment.
- Features UL Classified and FM Approved domestic outside stem and yoke (OSY) resilient seated gate valves.
- Patented torsion spring check provides lowest pressure loss and unmatched ease of serviceability.
- Replaceable check disc rubber for easy maintenance.
- Bottom mounted cast stainless steel relief valve.
- Metered bypass with a cubic foot per minute meter detects leakage or unauthorized water use from the fire sprinkler system.
- Integrated flood sensor with SentryPlus Alert technology detects excessive water discharges from the relief valve.
- Flood alert feature is activated with an add-on sensor connection kit, compatible with BMS and cellular network communication, and the Sensor Control Monitor for integration with BAS via RS-485 Modbus or Nexa platform by Wi-Fi.
Specifications
- Product Type: Reduced Pressure Detector Assembly
- Size: 8 inch
- Model Series: 957RPDA
- Pattern: N-pattern
- Shutoff Valves: Domestic Outside Stem and Yoke (OSY) resilient seated gate valves
- Bypass Meter: Cubic Feet Meter (CFM)
- Flood Sensor: Included, SentryPlus Alert technology
Materials
- Housing & Sleeve: 304 (Schedule 40) stainless steel
- Elastomers: EPDM, silicone, and Buna 'N'
- Torsion Spring Checks: Noryl®, stainless steel
- Check Discs: Reversible silicone or EPDM
- Test Cocks: Lead Free* bronze body
- Pins & Fasteners: 300 Series stainless steel
- Springs: Stainless steel
- Relief Valve: Bottom mounted cast stainless steel
Pressure - Temperature
- Temperature Range: 33°F – 140°F (0.5°C – 60°C)
- Maximum Working Pressure: 175 psi (12.1 bar)
Certificates & Approvals
- UL Classified
- FM Approved
- ASSE 1047
- CSA B64.4
- Approved by The Foundation for Cross-Connection Control and Hydraulic Research at The University of Southern California (FCCCHR-USC)
- AWWA C511-97