8 C400N-DOSY-FS

Item Number: F0206493
Skip to product information
1 of 1
Regular price $24,798.75
Special Order
When Will it Ship: Contact for Lead Time
Estimated transit time: 2 to 5 Business Days

Brand - Ames

  • Assembly Size: 8 inch
  • Weight: 709.0 lb
  • Body Material: Type 304 Stainless Steel
  • Valve Type: Domestic OSY Shutoff Valves
  • Pressure Rating: 175 PSI Max Working
  • Temperature Range: 33°F - 140°F
  • Flood Sensor: SentryPlus Alert® Technology
  • Installation: Horizontal N-Pattern
  • Lead Content: Less than 0.25%

Description

The 8 inch Colt C400N-DOSY-FS Reduced Pressure Zone backflow preventer is a Lead Free* assembly designed to protect potable water supplies from contamination caused by backsiphonage or backpressure. Featuring a durable 304 stainless steel body and domestic outside stem and yoke (OSY) gate valves, it's approved for health hazard applications. This compact unit includes a flood sensor with SentryPlus Alert® technology for discharge detection. It operates at 175 PSI max working pressure and is suitable for horizontal N-pattern installation. An add-on connection kit is required for flood sensor alerts.

Help Me Connect

This 8 inch reduced pressure zone backflow preventer assembly is designed for horizontal N pattern installation. It features groove couplings on the inlet and outlet, allowing for easy installation and precise alignment with your existing piping system. The OSY shutoff valves are integral to the assembly for positive shutoff. Ensure local plumbing codes are followed for proper installation, including any air gap requirements for drain lines.

View full details

Collapsible content

Additional Details

The Colt™ 8 inch stainless steel Reduced Pressure Zone (RPZ) backflow preventer assembly is designed to prevent the reverse flow of fire protection substances and non-potable water from entering the potable water supply. It protects against contamination due to backsiphonage and backpressure, making it ideal for health hazard applications and continuous pressure piping systems.

This assembly features Lead Free* construction, complying with installation requirements.

Construction & Design

  • Features a Type 304 (Schedule 40) stainless steel housing and sleeve for durability.
  • Composed of two independent Link Check modules, a differential pressure relief valve, and two drip tight shutoff valves.
  • Includes domestic outside stem and yoke (OSY) resilient seated gate valves.
  • Groove couplings enable easy installation and integral pipeline adjustment.
  • Extremely compact design allows for use in smaller enclosures.
  • Equipped with a bottom mounted pressure relief valve.

Flood Sensor Technology

  • Integrated flood sensor with SentryPlus Alert® technology detects excessive water discharges from the relief valve.
  • When paired with an add-on connection kit (sold separately), the sensor activates to relay alerts for potential flooding events.
  • Connection kit options include BMS, cellular communication, and the Sensor Control Monitor for integration with BAS via RS-485 Modbus or the Nexa® platform through Wi-Fi.

NOTICE: An add-on connection kit is required to activate the flood sensor for communication. Without the connection kit, the flood sensor is a passive component. Watts® is not responsible for the failure of alerts due to connectivity issues, power outages, or improper installation.

Specifications

  • Body Material: Type 304 (Schedule 40) Stainless Steel
  • Assembly Size: 8 inch
  • Valve Type: Domestic Outside Stem and Yoke (OSY) Resilient Seated Gate Valves
  • Check Modules: Two Independent Link Checks
  • Elastomers: EPDM, Silicone, Buna 'N'
  • Check Discs: Reversible Silicone or EPDM
  • Test Cocks: Lead Free* Bronze Body
  • Pins & Fasteners: 300 Series Stainless Steel
  • Springs: Stainless Steel
  • Configuration: Horizontal N-Pattern Installation
  • Temperature Range: 33°F - 140°F (0.5°C - 60°C)
  • Maximum Working Pressure: 175 psi (12.1 bar)
  • Wetted Surface Lead Content: Less than 0.25%

Certificates & Approvals

  • Approved by the Foundation for Cross-Connection Control and Hydraulic Research at The University of Southern California (FCCCHR-USC)
  • AWWA C511-97
  • ASSE 1013
  • CSA B64.4
  • UL Classified (BFG & OSY Only)
  • FM Approved (BFG & OSY Only)
  • NSF Certified to NSF/ANSI 61-G

FAQs

What is the primary purpose of this backflow preventer assembly?

This backflow preventer is designed to prevent the reverse flow of non-potable water or fire protection substances into the potable water supply, protecting against contamination from backsiphonage and backpressure.

What material is the housing of the C400N-DOSY-FS assembly made from?

The housing and sleeve of this assembly are constructed from durable Type 304 (Schedule 40) stainless steel, ensuring longevity and resistance to corrosion.

Does this backflow preventer include a flood sensor, and how does it work?

Yes, it includes a flood sensor with SentryPlus Alert® technology to detect excessive water discharges from the relief valve. To activate communication alerts, an add-on connection kit (sold separately) is required.

What installation configurations are supported for this 8 inch C400 series backflow preventer?

This assembly is approved for horizontal N-pattern installation. It features groove couplings for straightforward installation and pipeline adjustment.

What is the maximum operating pressure and temperature range for this device?

The maximum working pressure for this backflow preventer is 175 psi (12.1 bar), and it can operate within a temperature range of 33°F to 140°F (0.5°C to 60°C).