8 C500-DNRS-G-FS

Item Number: F0191647
Skip to product information
1 of 1
Regular price $25,821.55
Special Order
When Will it Ship: Contact for Lead Time
Estimated transit time: 2 to 5 Business Days

Brand - Ames

  • Size: 8 inch
  • Weight: 647.0 lb
  • Housing Material: 304 Stainless Steel
  • Maximum Working Pressure: 175 PSI
  • Temperature Range: 33°F - 140°F
  • Shutoff Valves: Resilient Seated Gate, Non-Rising Stem
  • Flood Sensor: SentryPlus Alert® Technology
  • Bypass Meter: Gallon per minute
  • Approvals: AWWA C511-97, ASSE 1047, CSA B64.4, cULus, FM Approved

Description

The Colt C500 8 inch Reduced Pressure Detector Backflow Preventer Assembly (SKU F0191647) is engineered to protect potable water supplies from contamination caused by backpressure or backsiphonage. This C500 series device is suitable for health-hazard cross-connections, including fire sprinkler systems. It features a durable 304 stainless steel housing, resilient seated gate valves, and a bottom-mounted relief valve. The assembly includes a metered bypass for leak detection and a SentryPlus Alert® flood sensor to detect excessive water discharge. With a compact, lightweight design, it offers unmatched serviceability and a maximum working pressure of 175 PSI.

Help Me Connect

This Colt™ C500 Reduced Pressure Detector Assembly is designed with groove fittings for straightforward installation and integral pipeline adjustment. The flood sensor feature requires an add-on connection kit to become active and communicate alerts.

Flood Sensor Connectivity Options

  • Add-on Connection Kit: Required to activate the flood sensor and enable communication.
  • Sensor Control Monitor: Integrates with Building Automation Systems (BAS) via RS-485 Modbus or the Nexa® platform through Wi-Fi connectivity.
  • Other Options: Compatibility with BMS and cellular communication solutions is available through various connection kits.

A retrofit sensor connection kit is also available for existing installations.

View full details

Collapsible content

Additional Details

This Colt™ 8 inch reduced pressure detector backflow preventer assembly provides protection against the reverse flow of fire protection substances and non-potable water into potable water supplies. It is ideal for safeguarding drinking water from dangerous cross-connections caused by backsiphonage or backpressure, commonly found in fire sprinkler systems and at service line entrances.

Key Features

  • Compact and Lightweight: Features an extremely compact design and is 70% lighter than traditional backflow preventers.
  • Durable Construction: Constructed with 304 (Schedule 40) stainless steel housing and sleeve for corrosion resistance.
  • Easy Installation & Service: Utilizes groove fittings for integral pipeline adjustment and features unmatched ease of serviceability with replaceable check disc rubber.
  • Efficient Flow: Patented link check design ensures the lowest pressure loss.
  • Leak Detection: Includes a metered bypass with a gallon per minute meter to detect underground leaks and unauthorized water use.
  • Flood Sensing: Equipped with a flood sensor with SentryPlus Alert® technology to detect excessive water discharges from the relief valve. When paired with an add-on connection kit, the sensor relays alerts for potential flooding events.
  • Reliable Shutoff Valves: Features drip tight resilient seated gate valves with non-rising stems.
  • Corrosion Resistant Relief Valve: Includes a bottom-mounted cast stainless steel relief valve.

A WARNING: It is illegal to use this product in a plumbing system providing water for human consumption, such as drinking or dishwashing, in the United States. Before installing, consult your local water authority, building, and plumbing codes.

Specifications

  • Product Type: Reduced Pressure Detector Assembly
  • Series: C500
  • Size: 8 inch
  • Housing & Sleeve Material: 304 (Schedule 40) Stainless Steel
  • Elastomers: EPDM, Silicone, Buna 'N'
  • Link Checks Material: Noryl®, Stainless Steel
  • Check Discs Material: Reversible Silicone or EPDM
  • Test Cocks Material: Lead Free* Bronze Body
  • Pins & Fasteners Material: 300 Series Stainless Steel
  • Springs Material: Stainless Steel
  • Shutoff Valves: Resilient Seated Gate Valves with Non-Rising Stem
  • Bypass Meter: Gallon per minute meter
  • Flood Sensor: SentryPlus Alert® Technology

Performance

  • Temperature Range: 33°F - 140°F (0.5°C - 60°C)
  • Maximum Working Pressure: 175 psi (12.1 bar)

Configurations

  • Horizontal

Certificates & Approvals

  • Approved by Foundation for Cross-Connection Control and Hydraulic Research at The University of Southern California (FCCCHR-USC)
  • AWWA C511-97
  • ASSE 1047
  • CSA B64.4
  • cULus Classified
  • FM Approved

FAQs

What is the primary purpose of the Colt C500 Reduced Pressure Detector Backflow Preventer Assembly?

Its primary purpose is to protect potable water supplies from contamination by preventing the reverse flow of non-potable water or fire protection substances due to backsiphonage or backpressure. It's designed for health-hazard cross-connections.

What is the maximum operating pressure and temperature range for this backflow preventer?

The maximum operating pressure is 175 psi (12.1 bar), and the temperature range is 33°F to 140°F (0.5°C to 60°C).

What materials are used in the construction of this backflow preventer?

The housing and sleeve are constructed from 304 (Schedule 40) stainless steel. Elastomers include EPDM, silicone, and Buna 'N', with Noryl® and stainless steel in the link checks, and lead-free bronze for test cocks.

How does the flood sensor function, and what is required to activate it?

The integrated flood sensor with SentryPlus Alert® technology detects excessive water discharges from the relief valve. To activate the sensor and enable it to communicate alerts, an add-on connection kit is required.

Is this product approved for use in residential drinking water systems?

No, a warning states it is illegal to use this product in a plumbing system providing water for human consumption, such as drinking or dishwashing, in the United States. Always consult local water authorities and codes before installation.