8 LF957RPDA-OSY-LM-FS
Item Number: F124840Brand - Watts
Couldn't load pickup availability
- Size: 8 inch
- Weight: 633.0 lb
- Housing Material: 304 Stainless Steel
- Maximum Working Pressure: 175 PSI
- Temperature Range: 33°F - 110°F
- Lead Free* Construction
- Flood Sensor with SentryPlus Alert® Technology
- UL and FM Approved OSY Resilient Seated Gate Valves
- Extremely Compact and Lightweight Design
Description
Description
Help Me Connect
Help Me Connect
Flood Sensor Activation & Monitoring
The integrated flood sensor requires an add-on connection kit to be fully activated. Without this kit, the sensor operates as a passive component and does not communicate with other devices. When activated, the sensor can relay alerts for excessive water discharge from the relief valve, helping facility personnel to take corrective action and prevent costly damage.
- Connection kit options include those compatible with Building Management Systems (BMS).
- Other options enable cellular communication for remote alerts.
- The Sensor Control Monitor allows integration with Building Automation Systems (BAS) via RS-485 Modbus or the Nexa® platform through Wi-Fi connectivity.

Collapsible content
Additional Details
This 8 inch reduced pressure detector backflow preventer assembly provides protection to the potable water system from contamination caused by backpressure or backsiphonage, especially where health hazards exist. It is designed for horizontal installation.
The assembly features a 304 (Schedule 40) stainless steel housing and sleeve, two independent torsion spring check modules, a corrosive-resistant bottom mounted pressure relief valve, and resilient seated outside stem and yoke (OSY) gate valves. It is designed for ease of serviceability with a quick access sleeve and replaceable check disc rubber.
Flood Detection
- Includes a flood sensor with SentryPlus Alert® technology to detect continuous discharge from the relief valve.
- An add-on connection kit is required to activate the flood sensor, enabling it to relay alerts for potential flooding events.
- Compatible connection kit options include BMS, cellular communication, and the Sensor Control Monitor which integrates with Building Automation Systems (BAS) via RS-485 Modbus or the Nexa® platform through Wi-Fi.
Use of the flood sensor does not replace the need to comply with all required instructions, codes, and regulations related to installation, operation, and maintenance of this product, including the need to provide proper drainage in the event of a discharge.
Specifications
General
- Product Type: Reduced Pressure Detector Backflow Preventer Assembly
- Size: 8 inch
- Shutoff Valves: UL and FM Approved Outside Stem and Yoke (OSY) Resilient Seated Gate Valves
- Relief Valve: Bottom Mounted Cast Stainless Steel
- Flood Sensor: SentryPlus Alert® Technology on Relief Valve
- Construction: Lead Free*
- Design: Extremely Compact, 70% lighter than traditional designs
Materials
- Housing & Sleeve: 304 (Schedule 40) Stainless Steel
- Elastomers: EPDM, Silicone, Buna 'N'
- Torsion Spring Checks: Noryl®, Stainless Steel
- Check Discs: Reversible Silicone or EPDM Rubber
- Test Cocks: Lead Free* Bronze Body
- Pins & Fasteners: 300 Series Stainless Steel
- Springs: Stainless Steel
Performance
- Temperature Range: 33°F - 110°F (0.5°C - 43°C)
- Maximum Working Pressure: 175 PSI (12.1 bar)
Certificates & Approvals
- ASSE 1047
- AWWA C511-97
- CSA B64.4
- FM Approved
- NSF/ANSI 372 Certified
- UL Classified