8 LF957RPDA-OSY-LM-FS

Item Number: F124840
Skip to product information
1 of 1
Regular price $23,943.00
Special Order
When Will it Ship: Contact for Lead Time
Estimated transit time: 2 to 5 Business Days

Brand - Watts

  • Size: 8 inch
  • Weight: 633.0 lb
  • Housing Material: 304 Stainless Steel
  • Maximum Working Pressure: 175 PSI
  • Temperature Range: 33°F - 110°F
  • Lead Free* Construction
  • Flood Sensor with SentryPlus Alert® Technology
  • UL and FM Approved OSY Resilient Seated Gate Valves
  • Extremely Compact and Lightweight Design

Description

The Watts Series LF957RPDA is an 8 inch Lead Free Reduced Pressure Detector Backflow Preventer Assembly designed to protect potable water systems from contamination due to backpressure or backsiphonage. This compact unit features a 304 stainless steel housing, UL and FM approved OSY gate valves, and an integrated SentryPlus Alert flood sensor for detecting relief valve discharge. It is 70% lighter than traditional designs, making installation easier. Approved by ASSE, AWWA, CSA, FM, NSF, and UL, it ensures reliable health hazard protection. Item number F124840.

Help Me Connect

Flood Sensor Activation & Monitoring

The integrated flood sensor requires an add-on connection kit to be fully activated. Without this kit, the sensor operates as a passive component and does not communicate with other devices. When activated, the sensor can relay alerts for excessive water discharge from the relief valve, helping facility personnel to take corrective action and prevent costly damage.

  • Connection kit options include those compatible with Building Management Systems (BMS).
  • Other options enable cellular communication for remote alerts.
  • The Sensor Control Monitor allows integration with Building Automation Systems (BAS) via RS-485 Modbus or the Nexa® platform through Wi-Fi connectivity.
View full details

Collapsible content

Additional Details

This 8 inch reduced pressure detector backflow preventer assembly provides protection to the potable water system from contamination caused by backpressure or backsiphonage, especially where health hazards exist. It is designed for horizontal installation.

The assembly features a 304 (Schedule 40) stainless steel housing and sleeve, two independent torsion spring check modules, a corrosive-resistant bottom mounted pressure relief valve, and resilient seated outside stem and yoke (OSY) gate valves. It is designed for ease of serviceability with a quick access sleeve and replaceable check disc rubber.

Flood Detection

  • Includes a flood sensor with SentryPlus Alert® technology to detect continuous discharge from the relief valve.
  • An add-on connection kit is required to activate the flood sensor, enabling it to relay alerts for potential flooding events.
  • Compatible connection kit options include BMS, cellular communication, and the Sensor Control Monitor which integrates with Building Automation Systems (BAS) via RS-485 Modbus or the Nexa® platform through Wi-Fi.

Use of the flood sensor does not replace the need to comply with all required instructions, codes, and regulations related to installation, operation, and maintenance of this product, including the need to provide proper drainage in the event of a discharge.

Specifications

General

  • Product Type: Reduced Pressure Detector Backflow Preventer Assembly
  • Size: 8 inch
  • Shutoff Valves: UL and FM Approved Outside Stem and Yoke (OSY) Resilient Seated Gate Valves
  • Relief Valve: Bottom Mounted Cast Stainless Steel
  • Flood Sensor: SentryPlus Alert® Technology on Relief Valve
  • Construction: Lead Free*
  • Design: Extremely Compact, 70% lighter than traditional designs

Materials

  • Housing & Sleeve: 304 (Schedule 40) Stainless Steel
  • Elastomers: EPDM, Silicone, Buna 'N'
  • Torsion Spring Checks: Noryl®, Stainless Steel
  • Check Discs: Reversible Silicone or EPDM Rubber
  • Test Cocks: Lead Free* Bronze Body
  • Pins & Fasteners: 300 Series Stainless Steel
  • Springs: Stainless Steel

Performance

  • Temperature Range: 33°F - 110°F (0.5°C - 43°C)
  • Maximum Working Pressure: 175 PSI (12.1 bar)

Certificates & Approvals

  • ASSE 1047
  • AWWA C511-97
  • CSA B64.4
  • FM Approved
  • NSF/ANSI 372 Certified
  • UL Classified

FAQs

What is the primary function of the Watts LF957RPDA backflow preventer?

Its primary function is to protect potable water systems from contamination due to backpressure or backsiphonage, particularly in applications where health hazards exist.

What does "Lead Free" construction mean for this product?

"Lead Free" construction indicates that the wetted surface of this product, which contacts consumable water, contains less than 0.25% of lead by weight, complying with lead-free installation requirements.

How does the SentryPlus Alert flood sensor operate?

The SentryPlus Alert flood sensor detects excessive water discharges from the relief valve. To activate its alert capabilities, an add-on connection kit must be installed, which then enables the sensor to relay notifications.

What are the connectivity options for the flood sensor alerts?

When an add-on connection kit is installed, the flood sensor can be integrated with Building Management Systems (BMS), cellular communication networks, or a Sensor Control Monitor for BAS integration via RS-485 Modbus or the Nexa® platform via Wi-Fi.

What are the main materials used in the construction of this assembly?

The housing and sleeve are made from 304 (Schedule 40) stainless steel. Other key materials include EPDM, silicone, and Buna 'N' for elastomers, Noryl® and stainless steel for torsion spring checks, and Lead Free* bronze for test cocks.