Brand - Febco

  • Nominal Size: 1 1/2 inch
  • Body Material: Bronze
  • Maximum Working Pressure: 175 psi
  • Temperature Range: 32°F to 140°F
  • Flood Detection: Integrated SentryPlus Alert® sensor
  • Shutoff Valves: Quarter Turn Ball
  • Approvals: ASSE 1013, CSA B64.4
  • Application: High hazard non-potable service

Description

The FEBCO Series 860 1 1/2 inch Reduced Pressure Zone Backflow Preventer is designed for high-hazard applications to protect potable water from contamination due to backsiphonage or backpressure. This bronze assembly features quarter-turn shutoff valves, test cocks, and a SentryPlus Alert® flood sensor to detect continuous discharge from the relief valve. The sensor requires an add-on connection kit for active monitoring and alert transmission via BMS, cellular, or Wi-Fi. It is rated for a maximum working pressure of 175 psi and a temperature range of 32°F to 140°F. Ideal for industrial, hospital, and irrigation systems. Item F1315.

Help Me Connect

Connections

  • This assembly features NPT ANSI/ASME B1.20.1 threaded end connections for easy installation into piping systems.
  • The integrated flood sensor requires an add-on sensor connection kit (sold separately) for activation and communication.
  • Compatible connection kit options include those supporting BMS (Building Management Systems), cellular communication, or integration with BAS (Building Automation Systems) via RS-485 Modbus or the Nexa® platform through Wi-Fi.
View full details

Collapsible content

Additional Details

The FEBCO Series 860 1 1/2 inch Reduced Pressure Zone Backflow Preventer assembly protects drinking water supplies from dangerous cross-connections, preventing reverse flow of high hazard fluids into the potable water supply due to backsiphonage or backpressure.

It is suitable for use in industrial plants, hospitals, irrigation systems, boiler feed lines, and other non-potable service applications requiring maximum protection.

Features

  • Includes SentryPlus Alert® technology with an integrated flood sensor to detect continuous discharge from the relief valve.
  • Enables flood monitoring and alerts when paired with an add-on sensor connection kit (sold separately).
  • Sensor connection kit options include compatibility with BMS, cellular communication, or the Nexa® platform via Wi-Fi for integration with BAS.
  • Features a durable bronze body with top entry access.
  • Equipped with modular relief valve and check valves for easy maintenance.
  • Includes quarter turn shutoff ball valves and top-mounted test cocks.

Components

  • Two independently operating, spring-loaded check valves.
  • A pressure differential relief valve located between the check valves.
  • Bronze body, caps, and relief valve body/cover.
  • Two quarter turn shutoff valves and four test cocks.

WARNING: It is illegal to use this product in any plumbing system providing water for human consumption, such as drinking or dishwashing, in the United States. Always consult local water authority, building, and plumbing codes before installation.

NOTICE: An add-on sensor connection kit is required to activate the flood sensor's alert features. Without this kit, the sensor acts as a passive component without communication capability.

NOTICE: The flood sensor is an alert system and does not replace the need to comply with all installation, operation, and maintenance codes and regulations, including providing proper drainage for discharge.

NOTICE: Always read all installation instructions and product safety information thoroughly before beginning installation. Consult governing authorities for local installation requirements.

Specifications

General

  • Nominal Size: 1 1/2 inch
  • Body Material: Bronze
  • End Connections: NPT ANSI/ASME B1.20.1
  • Shutoff Valves: Quarter Turn Ball Valves
  • Test Cocks: Included
  • Flood Detection: Integrated Flood Sensor with SentryPlus Alert® Technology

Pressure & Temperature

  • Maximum Working Pressure: 175 psi (12.1 bar)
  • Hydrostatic Test Pressure: 350 psi (24.1 bar)
  • Temperature Range: 32°F to 140°F (0°C to 60°C)

Internal Materials

  • Valve Body: Bronze
  • Elastomers: Silicone
  • Springs: Stainless steel
  • Seats: Noryl®
  • Seat Discs: Silicone Rubber/SS
  • Diaphragms: Rubber/Fabric

Certificates & Approvals

  • ANSI/AWWA Conformance (C511)
  • Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California
  • ASSE 1013
  • CSA B64.4

FAQs

What is the primary purpose of the FEBCO Series 860 backflow preventer?

The primary purpose is to protect potable drinking water supplies from contamination by preventing the reverse flow of high-hazard (toxic) fluids due to backsiphonage or backpressure.

What applications is this backflow preventer suitable for?

It is suitable for non-potable service applications such as industrial plants, hospitals, irrigation systems, boiler feed lines, morgues, mortuaries, and chemical plants, or any installation requiring maximum protection against cross-connections.

How does the flood sensor feature work?

The integrated flood sensor with SentryPlus Alert® technology detects excessive water discharges from the relief valve. To activate alert notifications, an add-on sensor connection kit is required, which enables communication via BMS, cellular, or Wi-Fi.

What are the pressure and temperature limits for this assembly?

This backflow preventer has a maximum working pressure of 175 psi (12.1 bar) and can operate within a temperature range of 32°F to 140°F (0°C to 60°C).

Are there any legal restrictions for using this product?

Yes, it is illegal to use this product in any plumbing system providing water for human consumption, such as drinking or dishwashing, in the United States. Always consult local water authorities and codes before installation.