4 LF886V-LG-GPM-FS
Item Number: F683200
1
/
of
1
Regular price
$10,083.75
Special Order
When Will it Ship:
Contact for Lead Time
Estimated transit time: 2 to 5 Business Days
Brand - Febco
Couldn't load pickup availability
- Nominal Size: 4 inch
- Weight: 172.0 lb
- Lead Free construction
- Body Material: Ductile Iron
- ArmorTek® corrosion-resistant coating
- SentryPlus Alert® flood sensor for relief valve discharge
- GPM metered bypass for leak detection
- Maximum Working Pressure: 175 psi
- Temperature Range: 33°F to 140°F
Description
Description
This 4 inch FEBCO LF886V lead free Reduced Pressure Zone Detector Backflow Preventer Assembly protects potable water systems from high hazard contamination due to backpressure or backsiphonage. Designed for industrial applications, it features a durable ductile iron body with ArmorTek® corrosion-resistant coating and stainless steel check components. An integrated SentryPlus Alert® flood sensor detects relief valve discharge, requiring an add-on connection kit for active alerts. The assembly includes a GPM metered bypass to monitor for leaks or unauthorized water usage. It is ASSE 1047 and IAPMO/CUPC approved, with a 175 psi maximum working pressure and 33°F to 140°F temperature range.
Help Me Connect
Help Me Connect
Connections & Compatibility
- The backflow preventer's end connections are compliant with ASME B16.1 Class 125 and AWWA Class D Flange standards.
- The integrated SentryPlus Alert® flood sensor requires an add-on connection kit for activation and communication. Without this kit, the sensor operates passively.
- Connection kit options include those for Building Automation Systems (BMS), cellular communication, or the Sensor Control Monitor for integration via RS-485 Modbus or the Nexa® platform (Wi-Fi).

Collapsible content
Additional Details
This 4 inch lead free MasterSeries® LF886V Reduced Pressure Zone Detector Backflow Preventer Assembly is designed to protect against backpressure and backsiphonage conditions for high hazard/toxic applications in potable drinking water systems, particularly in industrial installations.
This N-pattern assembly is supplied without shutoff valves and includes a gallons per minute (GPM) metered bypass and ball valve test cocks. Please note: The assembly configured without shutoff valves is not a UL Classified or FM Approved configuration.
Advanced Protection Features
- The backflow preventer's iron components are coated with ArmorTek®, a patented three-part advanced epoxy system. This coating is engineered to reduce microbial-induced corrosion (MIC) and protect exposed metal substrate for extended durability.
- Features a flood sensor with SentryPlus Alert® technology to detect excessive water discharges from the relief valve. When paired with an add-on connection kit, the sensor activates to relay alerts for potential flooding events.
- Equipped with a stainless steel relief valve seat and stainless steel check components for maximum performance and durability.
- The bypass line includes a 5/8 inch x 3/4 inch water meter compliant with ANSI/AWWA C700, designed to detect potential underground water leaks or unauthorized water usage.
Design and Construction
- Ductile iron valve body design ensures robust construction.
- Inline serviceable assembly means no special tools are required for maintenance.
- Includes captured modular spring assembly, reversible and replaceable discs, and field replaceable seats.
Specifications
General
- Product Type: Reduced Pressure Zone Detector Backflow Preventer Assembly
- Nominal Size: 4 inch
- Pattern: N-Pattern (Horizontal)
- Lead Free: Yes (wetted surface contains less than 0.25% lead by weight)
- Shutoff Valves: Not included
- Bypass: GPM Metered (5/8 inch x 3/4 inch water meter)
- Flood Detection: SentryPlus Alert® Flood Sensor included
Materials
- Main Valve Body: Ductile Iron Grade 65-45-12
- Relief Valve Body: Ductile Iron Grade 65-45-12
- Coating: ArmorTek® Powder Coating (internal and external surfaces)
- Check Seats: Stainless Steel
- Relief Valve Seat: Stainless Steel
- Disc Holder: Stainless Steel
- Elastomer Disc: Silicone
- Spring: Stainless Steel
- Clamp: AWWA C606
Performance
- Maximum Working Pressure: 175 psi
- Minimum Working Pressure: 20 psi
- Hydrostatic Test Pressure: 350 psi
- Hydrostatic Safety Pressure: 700 psi
- Temperature Range: 33°F - 140°F (0.5°C - 60°C) continuous
Certificates & Approvals
- Foundation for Cross-Connection Control and Hydraulic Research (FCCCHR-USC)
- ASSE 1047
- CSA B64.4
- IAPMO/CUPC
- AWWA Standard C511 Compliant
- End Connections: Compliant to ASME B16.1 Class 125 & AWWA Class D Flange
- Note: This assembly, configured without shutoff valves, is not UL Classified or FM Approved.
FAQs
What is the primary use of the FEBCO LF886V Reduced Pressure Zone Detector Backflow Preventer?
This backflow preventer is designed to protect potable drinking water systems from contamination due to backpressure and backsiphonage conditions. It is ideal for high hazard/toxic applications, particularly in industrial installations where local codes mandate protection.
What does "Lead Free" signify for this backflow assembly?
The "Lead Free" designation means that the wetted surface of this product, which comes into contact with consumable water, contains less than 0.25% of lead by weight. This complies with low lead installation requirements and relevant state codes.
How does the ArmorTek® coating protect the backflow preventer?
The ArmorTek® coating is a patented three-part advanced epoxy system applied to the iron components. It is engineered to reduce microbial-induced corrosion (MIC) and protect exposed metal substrates, enhancing the durability and lifespan of the assembly.
Is this particular configuration (LF886V-LG) approved by UL or FM?
No, this specific assembly, configured without shutoff valves (LG), is not a UL Classified or FM Approved configuration. UL Classified and FM Approved configurations typically include OS&Y RW gate valves.
How does the SentryPlus Alert® flood sensor provide warnings?
The SentryPlus Alert® flood sensor detects excessive water discharges from the relief valve. To activate and relay alerts (via call, email, or text), an add-on connection kit is required. Without the kit, the sensor operates as a passive component.
Related Products
1
/
of
2