6 LF886-WZ-DOSY-LM-FS

Item Number: F8007417
Skip to product information
1 of 1
Regular price $25,588.50
Special Order
When Will it Ship: Contact for Lead Time
Estimated transit time: 2 to 5 Business Days

Brand - Febco

  • 6 inch Lead Free Reduced Pressure Zone Detector Assembly (Type II)
  • Weight: 530.0 lb
  • Ductile iron body with ArmorTek advanced epoxy coating for corrosion resistance
  • Z-pattern lay-length for competitor drop-in replacement
  • Stainless steel relief valve seat and check components for maximum durability
  • Integrated flood sensor with SentryPlus Alert® technology
  • Equipped with UL Classified and FM Approved OS&Y shutoff valves
  • Maximum Working Pressure: 175 PSI
  • Temperature Range: 33°F – 140°F

Description

The FEBCO 6 inch LF886-WZ Lead Free Reduced Pressure Zone Detector Backflow Preventer is designed to protect potable water systems from high hazard (toxic) fluids caused by backpressure and backsiphonage. Its ductile iron body features ArmorTek corrosion-resistant coating for enhanced durability, while stainless steel relief valve seats and check components ensure long-lasting performance. This assembly offers a Z-pattern lay-length for convenient competitor drop-in replacement and includes an integrated flood sensor with SentryPlus Alert technology to detect relief valve discharge. Equipped with OS&Y shutoff valves and a litres per minute meter, it is ideal for industrial installations. Item number F8007417.

Help Me Connect

Connections

  • Designed for Z-pattern lay-length for drop-in replacement of competitor backflow preventers.
  • Equipped with UL Classified and FM Approved OS&Y gate valves and ball valve test cocks.
  • End connections comply with ASME B16.1 Class 125 and AWWA Class D Flange standards.

Flood Sensor Integration

  • The integrated flood sensor requires an add-on connection kit for activation.
  • Connection kit options allow integration with Building Management Systems (BMS), cellular communication, or the Sensor Control Monitor for BAS via RS-485 Modbus or the Nexa® platform through Wi-Fi.
View full details

Collapsible content

Additional Details

This 6 inch MasterSeries® LF886W/WZ Reduced Pressure Zone Detector backflow preventer assembly provides critical protection against high hazard (toxic) fluids in potable water systems, safeguarding against both backpressure and backsiphonage conditions in industrial installations.

This assembly features a longer lay-length for drop-in replacement of competitor's Z-pattern valves. It is constructed with a ductile iron body, UL Classified and FM Approved domestic outside stem and yoke (OS&Y) shutoff valves, replaceable stainless steel check seats, and ball valve test cocks. Enhanced with a stainless-steel relief valve seat and stainless-steel check components, this assembly offers superior dependability and extended service life.

Flood Detection

  • Includes an integrated flood sensor with SentryPlus Alert® technology designed to detect excessive water discharges from the relief valve.
  • An add-on connection kit is required to activate the flood sensor. Without the connection kit, the flood sensor is a passive component that does not communicate with any other device.
  • When activated, the sensor relays alerts for potential flooding events. Connection kit options include Building Management Systems (BMS), cellular communication, or the Sensor Control Monitor for integration with BAS via RS-485 Modbus or the Nexa® platform by Wi-Fi connectivity.

Main Valve Features

  • Stainless steel relief valve seat and stainless steel check components for maximum performance and durability.
  • Longer gate-to-gate length for drop-in replacement of longer valves.
  • Inline serviceable assembly; no special tools required.
  • Captured modular spring assembly.
  • Reversible and replaceable discs.
  • Field replaceable seats.
  • Ductile iron valve body design.
  • ArmorTek® coating technology to resist corrosion of internals.
  • Modular and repairable pressure differential relief valve.
  • Clapper check assembly.
  • Captured O-ring design.

Auxiliary Bypass Features

  • Compact design; remains in main valve assembly profile.
  • Inline serviceable 3/4" check assembly; no special tools required.
  • Field replaceable seat and disc.
  • Designed to detect potential underground water leaks and unauthorized water usage.

Specifications

  • Size: 6 inch
  • Lay Length: Z-Pattern (Competitor Drop-in Replacement)
  • Type: Reduced Pressure Zone Detector Assembly (Type II)
  • Lead Content: Lead Free (less than 0.25% by weight)
  • Shutoff Valves: OS&Y Gate Valves (Domestic, UL Classified and FM Approved)
  • Meter: Litres Per Minute Meter

Materials

  • Main Valve Body: Ductile Iron Grade 65-45-12
  • Relief Valve Body: Ductile Iron Grade 65-45-12
  • Coating: Armor-Tek powder coating (internal and external surfaces)
  • Check Seats: Stainless steel
  • Relief Valve Seat: Stainless steel
  • Disc Holder: Stainless steel
  • Diaphragm/Disc: Silicone
  • Spring: Stainless steel
  • Clamp: AWWA C506

Pressure & Temperature

  • Max. Working Pressure: 175 PSI (12.1 bar)
  • Min. Working Pressure: 20 PSI (1.4 bar)
  • Hydrostatic Test Pressure: 350 PSI (24.1 bar)
  • Hydrostatic Safety Pressure: 700 PSI (48.3 bar)
  • Temperature Range: 33°F – 140°F (0.5°C – 60°C) (continuous)

Certificates & Approvals

  • Foundation for Cross-Connection Control and Hydraulic Research at The University of Southern California (FCCCHR-USC)
  • ASSE 1047
  • UL Classified (US & Canada)
  • FM Approved
  • IAPMO/CUPC
  • AWWA Standard C511 Compliant
  • CSA B64.4
  • End Connections: Compliant to ASME B16.1 Class 125 & AWWA Class D Flange

FAQs

What is the primary function of the FEBCO 6 inch LF886-WZ backflow preventer?

This backflow preventer is designed to protect potable drinking water systems from contamination by high hazard (toxic) fluids due to backpressure and backsiphonage, commonly found in industrial installations and applications.

What does 'Lead Free' mean for this product?

The 'Lead Free' designation means that the wetted surfaces of this product that come into contact with consumable water contain less than 0.25% of lead by weight, complying with low lead installation requirements.

How does the integrated flood sensor operate?

The flood sensor with SentryPlus Alert technology detects excessive water discharges from the relief valve. An add-on connection kit is required to activate the sensor, enabling it to relay alerts through options like BMS, cellular communication, or the Nexa® platform via Wi-Fi.

What are the key material components and protective coating of this backflow preventer?

The main valve body and relief valve body are made from Ductile Iron Grade 65-45-12. These components are protected with ArmorTek®, a patented three-part advanced epoxy coating system engineered to resist microbial-induced corrosion (MIC).

What are the maximum operating pressure and continuous temperature range for this device?

The maximum working pressure for this backflow preventer is 175 PSI (12.1 bar). It has a continuous temperature range of 33°F to 140°F (0.5°C to 60°C).