8 994-LF-FS
Item Number: F438066Brand - Watts
Couldn't load pickup availability
- 8 Inch Reduced Pressure Zone (RPZ) Backflow Preventer
- Weight: 179.0 lb
- Lead-Free Stainless Steel Body and Internal Parts
- Includes Flood Sensor with SentryPlus Alert Technology
- Designed without Shutoff Valves (LF Model)
- Maximum Working Pressure: 175 PSI
- Temperature Range: 33°F-110°F
- Compact, Short Lay Length Design
- No Special Tools Required for Servicing
Description
Description
Help Me Connect
Help Me Connect
Flood Sensor Connection
- The integrated flood sensor is a passive component until activated with an add-on sensor connection kit.
- The add-on connection kit enables the flood sensor to relay signals to facility personnel for corrective action.
- The add-on sensor connection kit is compatible with Building Management Systems (BMS) and cellular network communication.
- A retrofit sensor connection kit is also available for existing installations.
NOTICE: Watts recommends installing a drain line and the required 994AGK-P air gap for proper drain line installation when installing an air gap. Attach the air gap brackets directly onto the flood sensor.

Collapsible content
Additional Details
The Watts Series 994 Reduced Pressure Zone (RPZ) Assembly Backflow Preventer is an 8 inch lead-free device designed to protect potable water supplies from health hazard cross-connections caused by backpressure or backsiphonage. This model is supplied without shutoff valves and features a compact, modular design for straightforward in-line maintenance.
This assembly incorporates a flood sensor with SentryPlus Alert technology to detect excessive water discharges from the relief valve. When activated with an optional add-on sensor connection kit, the sensor relays a signal for notification of potential flooding, helping to prevent costly damage.
Features
- Stainless steel construction throughout the body and internal metal parts ensures long-term corrosion resistance and maximum strength.
- Features a short lay length and lightweight stainless steel body, reducing installation and shipping costs.
- Bottom-mounted relief valve minimizes clearance requirements, ideal for installations against an outside wall.
- Patented torsion spring check valves provide maximum flow and low pressure drop for efficient operation.
- No special tools are required for servicing, simplifying maintenance procedures.
- Compact construction allows for installation in smaller enclosures.
- Equipped with a flood sensor on the relief valve for proactive discharge detection.
- Flood alert feature is activated with an add-on sensor connection kit, compatible with BMS and cellular network communication systems.
NOTICE: An add-on connection kit is required to activate the flood sensor. Without this kit, the flood sensor is a passive component and does not communicate with any other device. You are required to thoroughly read all installation instructions and product safety information before beginning the installation of this product.
Specifications
Materials
- Main Valve Body: 300 Series Stainless Steel
- All Internal Metal Parts: 300 Series Stainless Steel
- Check Assembly: Noryl®
Performance
- Maximum Working Pressure: 175 PSI (12.1 bar)
- Temperature Range: 33°F-110°F (0.5°C-43°C) continuous
Dimensions (8 Inch, without Shutoff Valves)
- Length (Dimension A): 52 1/2 inches (1334 mm)
- Weight (without Shutoff Valves): 179 lbs (81 kg)
- Flange Dimension: In accordance with AWWA Class D
Certificates & Approvals
- AWWA C511-92
- ASSE 1013
- CSA B64.5
FAQs
What is the primary purpose of the Watts Series 994 RPZ assembly?
Does this 8-inch model include shutoff valves?
How does the flood sensor work, and what is required for its activation?
What materials are used in the construction of this backflow preventer?
What are the maximum operating pressure and temperature limits for this device?
Related Products
-
Item Number: 0881396
Watts 994-ELF (vertical) Air Gap Elbow Fitting
Regular price $1,515.00Special Order -
-
-