Brand - Febco

  • Nominal Size: 8 inch
  • Weight: 835.0 lb
  • Lead Free: Yes (<0.25% lead by weight)
  • Body Material: Ductile Iron Grade 65-45-12
  • Coating: ArmorTek® advanced epoxy for MIC and corrosion resistance
  • Shutoff Valves: OSY resilient wedge gate valves
  • Flood Sensor: SentryPlus Alert® technology for discharge detection
  • Maximum Working Pressure: 175 PSI
  • Temperature Range: 33°F - 140°F

Description

The FEBCO MasterSeries LF866 is an 8 inch lead-free reduced pressure zone detector backflow preventer assembly designed to protect potable water supplies from high hazard contaminants due to backpressure and backsiphonage. Its ductile iron body features ArmorTek® advanced epoxy coating for superior corrosion resistance and extended durability. Equipped with OSY shutoff valves and a stainless steel relief valve seat, this assembly ensures reliable performance. An integrated SentryPlus Alert® flood sensor detects excessive discharges, offering enhanced monitoring capabilities when paired with an optional connection kit. Item number F683196.

Help Me Connect

Flood Sensor Connectivity

  • The integrated flood sensor requires an add-on connection kit to become active and relay alerts for potential flooding events.
  • Connection kit options include interfaces for BMS (Building Management Systems), cellular communication, or the Sensor Control Monitor.
  • The Sensor Control Monitor enables integration with BAS (Building Automation Systems) via RS-485 Modbus or the Nexa® platform through Wi-Fi.
  • Without an add-on connection kit, the flood sensor is a passive component and does not communicate with other devices.
View full details

Collapsible content

Additional Details

This 8 inch lead free FEBCO MasterSeries® Reduced Pressure Zone Detector Backflow Preventer Assembly is designed to protect potable drinking water systems from high hazard (toxic) fluids, preventing backpressure and backsiphonage in industrial and commercial installations.

The assembly features a flood sensor with SentryPlus Alert® technology to detect excessive water discharges from the relief valve.

Construction & Protection

  • Main valve body and relief valve body constructed from ductile iron Grade 65-45-12.
  • Features ArmorTek® coating, a patented three-part advanced epoxy system applied to internal and external surfaces to resist microbial-induced corrosion (MIC) and protect exposed metal substrate.
  • Designed with Lead Free construction, containing less than 0.25% lead by weight in wetted surfaces, to comply with low lead installation requirements.
  • Includes stainless steel relief valve seat and stainless steel check components for maximum performance and durability.
  • Equipped with OSY (Outside Stem and Yoke) resilient wedge gate shutoff valves.

Flood Sensor Technology

  • Integrated flood sensor detects continuous discharge from the relief valve.
  • Requires an add-on connection kit (sold separately) to activate the sensor for communication and alert relay.
  • Connection kit options include BMS, cellular communication, or the Sensor Control Monitor for integration with BAS via RS-485 Modbus or the Nexa® platform through Wi-Fi.
  • The flood sensor is a passive component without the connection kit and does not communicate with other devices. The flood sensor does not replace the need for proper drainage or compliance with installation codes.

Main Valve Features

  • Inline serviceable assembly requires no special tools for maintenance.
  • Captured modular spring assembly for easy servicing.
  • Features reversible and replaceable discs, and field replaceable seats.
  • Modular and repairable pressure differential relief valve.
  • Clapper check assembly with captured O-ring design.

Auxiliary Bypass

  • Compact design that remains within the main valve assembly profile.
  • Inline serviceable 3/4 inch check assembly, requiring no special tools.
  • Field replaceable seat and disc.
  • Helps detect potential underground water leaks and unauthorized water usage.

Specifications

  • Nominal Size: 8 inch
  • Product Type: Reduced Pressure Zone Detector Assembly
  • Detector Type: Backflow Preventer
  • Brand: FEBCO MasterSeries®
  • SKU: F683196
  • Model: LF866
  • End Connection Type: Flanged (Compliant to ASME B16.1 Class 125 & AWWA Class D Flange)
  • Lead Free: Yes (Wetted surface contains <0.25% lead)

Materials

  • Main Valve Body Material: Ductile iron Grade 65-45-12
  • Relief Valve Body Material: Ductile iron Grade 65-45-12
  • Coating: ArmorTek powder coating (internal and external surfaces)
  • Shutoff Valves: OSY resilient wedge gate valve (UL Classified and FM Approved)
  • Check Seats Material: Stainless steel
  • Relief Valve Seat Material: Stainless steel
  • Disc Holder Material: Stainless steel
  • Elastomer Disc Material: Silicone
  • Spring Material: Stainless steel

Performance & Operation

  • Maximum Working Pressure: 175 psi (12.1 bar)
  • Minimum Working Pressure: 20 psi (1.4 bar)
  • Hydrostatic Test Pressure: 350 psi (24.1 bar)
  • Hydrostatic Safety Pressure: 700 psi (48.3 bar)
  • Temperature Range: 33°F - 140°F (0.5°C ~ 60°C) continuous
  • Flow Orientation: Horizontal

Certificates & Approvals

  • Foundation for Cross-Connection Control and Hydraulic Research (FCCCHR-USC)
  • ASSE 1047
  • UL Classified (US & Canada)
  • FM Approved
  • IAPMO/CUPC
  • AWWA Standard C511 Compliant

FAQs

What is the primary purpose of the FEBCO MasterSeries LF866 backflow preventer?

The primary purpose is to protect potable drinking water systems from contamination due to backpressure and backsiphonage of high hazard (toxic) fluids, commonly used in industrial and commercial installations.

Is this backflow preventer suitable for all water systems?

It is primarily used on potable drinking water systems in applications where local governing codes mandate protection from non-potable quality water being pumped or siphoned back into the potable system. It is designed for high hazard/toxic applications.

What does "Lead Free" mean for this product?

"Lead Free" means that the wetted surface of this product, which comes into contact with consumable water, contains less than 0.25% of lead by weight, complying with low lead installation requirements.

How does the ArmorTek® coating benefit the backflow preventer?

The ArmorTek® coating is a patented three-part advanced epoxy system applied to internal and external surfaces of the ductile iron components. It is engineered to reduce microbial-induced corrosion (MIC) and protect exposed metal substrates, enhancing the assembly's durability and lifespan.

How does the integrated flood sensor work, and what is required to activate its alert features?

The integrated flood sensor with SentryPlus Alert® technology detects excessive water discharges from the relief valve. To activate its communication and alert relay features, an add-on connection kit (sold separately) is required. Without this kit, the sensor is passive and does not communicate.