Brand - Febco

  • Size: 8 inch
  • Weight: 662.0 lb
  • Model: LF886WZ Reduced Pressure Detector Assembly
  • Lay Length: Z-Pattern for competitor replacement
  • Material: Ductile Iron with ArmorTek® coating
  • Lead Free: Yes, wetted surfaces < 0.25% lead
  • Bypass Meter: Gallons Per Minute (GPM)
  • Flood Sensor: Integrated with SentryPlus Alert® technology
  • Maximum Working Pressure: 175 psi

Description

The FEBCO MasterSeries LF886WZ 8 inch Reduced Pressure Zone Detector Assembly is engineered to protect potable water systems from high hazard backpressure and backsiphonage conditions. Featuring a Z-pattern lay length, it serves as a direct drop-in replacement for competitor valves. Constructed with a durable ArmorTek® coated ductile iron body and stainless steel internal components, this assembly ensures maximum performance and corrosion resistance. It includes a GPM metered bypass and an integrated flood sensor with SentryPlus Alert® technology for early discharge detection. This lead free assembly is ideal for industrial installations requiring robust backflow prevention. Item number F8007424.

Help Me Connect

Compatibility & Installation

  • This FEBCO MasterSeries LF886WZ backflow preventer is specifically designed with a longer Z-pattern lay-length to allow for direct drop-in replacement of competitor Z-pattern valves, simplifying installation in existing configurations.
  • The assembly is supplied without shutoff valves (LG option), so appropriate 8 inch inlet and outlet shutoff valves must be provided separately for a complete installation.
  • The integrated flood sensor with SentryPlus Alert® technology requires an add-on connection kit for activation. Connection kit options include BMS, cellular communication, or the Sensor Control Monitor for integration with BAS via RS-485 Modbus or the Nexa® platform through Wi-Fi.
  • End connections are compliant to ASME B16.1 Class 125 and AWWA Class D Flange standards.
View full details

Collapsible content

Additional Details

This 8 inch lead free MasterSeries®, Z-pattern, reduced pressure detector backflow preventer assembly helps protect against high hazard (toxic) fluids in water services to industrial installations and applications.

This valve features a longer lay-length for drop-in replacement of competitor’s Z-pattern valves. The assembly without shutoff valves consists of a durable ductile iron body, replaceable stainless steel check seats, a gallons per minute (GPM) metered bypass, and ball valve test cocks. Improved with a stainless-steel relief valve seat, these rugged assemblies yield greater dependability and extended valve life.

Flood Detection & Alerts

  • Contains a flood sensor with SentryPlus Alert® technology to detect excessive water discharges from the relief valve.
  • When paired with an add-on connection kit, the sensor is activated to relay alerts for potential flooding events.
  • Connection kit options include BMS, cellular communication, and the Sensor Control Monitor which enables integration with BAS via RS-485 Modbus or the Nexa® platform through Wi-Fi.
  • An add-on connection kit is required to activate the flood sensor. Without the connection kit, the flood sensor is a passive component that does not communicate with any other device.

Construction & Design

  • ArmorTek® coating technology on all iron components protects against electrochemical corrosion and microbial-induced corrosion (MIC) on internal and external surfaces.
  • Features Lead Free construction to comply with low lead installation requirements (wetted surfaces contain less than 0.25% lead by weight).
  • Two independently acting approved clapper style check modules with replaceable seats and disc rubbers.
  • Inline serviceable assembly; no special tools required for servicing.
  • Captured modular spring assembly, reversible and replaceable discs, and field replaceable seats.
  • Modular and repairable pressure differential relief valve.
  • Auxiliary Bypass: Compact design, inline serviceable 3/4 inch check, no special tools for servicing, field replaceable seat and disc, detects potential underground leaks, and unauthorized water usage.

Specifications

  • Product Type: Reduced Pressure Zone Detector Assembly
  • Model Series: LF886WZ
  • Size: 8 inch
  • Pattern: Z-Pattern Lay Length
  • Shutoff Valves: Less Shutoff Valves (LG)
  • Bypass Meter: Gallons Per Minute (GPM)
  • Flood Sensor: Included (FS)
  • Test Cocks: Ball Valve Type

Materials

  • Main Valve Body: Ductile Iron Grade 65-45-12
  • Relief Valve Body: Ductile Iron Grade 65-45-12
  • Coating: ArmorTek Powder Coating (internal & external surfaces)
  • Check Seats: Stainless Steel
  • Relief Valve Seat: Stainless Steel
  • Disc Holder: Stainless Steel
  • Elastomer Disc: Silicone
  • Spring: Stainless Steel
  • Clamp: AWWA C606

Performance & Operating Conditions

  • Maximum Working Pressure: 175 psi (12.1 bar)
  • Minimum Working Pressure: 20 psi (1.4 bar)
  • Hydrostatic Test Pressure: 350 psi (24.1 bar)
  • Hydrostatic Safety Pressure: 700 psi (48.3 bar)
  • Temperature Range: 33°F - 140°F (0.5°C ~ 60°C) continuous

Certificates & Approvals

  • Foundation for Cross-Connection Control and Hydraulic Research at The University of Southern California (FCCCHR-USC)
  • ASSE 1047
  • UL Classified (US & Canada)
  • FM Approved
  • IAPMO/CUPC
  • AWWA Standard C511 Compliant
  • CSA B64.4
  • End Connections: Compliant to ASME B16.1 Class 125 & AWWA Class D Flange

FAQs

What is the primary function of this backflow preventer assembly?

This FEBCO MasterSeries LF886WZ assembly is designed to protect potable drinking water systems from backpressure and backsiphonage, specifically for high hazard (toxic) applications in industrial installations.

Does this backflow preventer include shutoff valves?

No, this specific model (LG option) is supplied without shutoff valves. Inlet and outlet shutoff valves would need to be sourced separately for a complete installation.

What is the significance of the Z-pattern lay length?

The Z-pattern lay length means this assembly is designed to be a direct drop-in replacement for competitor Z-pattern valves, simplifying installation and upgrades in existing systems.

How does the integrated flood sensor work?

The flood sensor with SentryPlus Alert® technology detects excessive water discharges from the relief valve. When paired with an add-on connection kit, it can relay alerts via BMS, cellular communication, or the Nexa® platform through Wi-Fi.

What materials are used in the construction to ensure durability and lead-free compliance?

The main and relief valve bodies are made of ductile iron (Grade 65-45-12) with ArmorTek® powder coating for corrosion resistance. Key internal components like check seats, relief valve seat, and springs are stainless steel, and the product is Lead Free, meaning wetted surfaces contain less than 0.25% lead by weight.