8 LF957NRPDA-OSY-LM-FS

Item Number: F124771
Skip to product information
1 of 1
Regular price $30,054.00
Special Order
When Will it Ship: Contact for Lead Time
Estimated transit time: 2 to 5 Business Days

Brand - Watts

  • Size: 8 inch
  • Weight: 706.0 lb
  • Lead Free Construction
  • Housing Material: 304 (Schedule 40) Stainless Steel
  • Shutoff Valves: UL/FM Approved OSY Gate Valves
  • Flood Detection: SentryPlus Alert® Flood Sensor
  • Installation: Horizontal N Pattern
  • Max Operating Pressure: 175 PSI
  • Temperature Range: 33°F - 110°F

Description

This 8 inch Lead Free Reduced Pressure Detector Backflow Preventer Assembly, Series LF957RPDA, protects potable water systems from contamination due to backpressure or backsiphonage, particularly in health hazard applications. Its compact and lightweight design features 304 stainless steel housing and UL/FM Approved OSY shutoff valves. A built-in flood sensor with SentryPlus Alert technology detects excessive relief valve discharges, offering crucial monitoring. Designed for horizontal N pattern installation, it incorporates patented torsion spring checks for low pressure loss and uses replaceable check disc rubber for easy maintenance. It is approved to ASSE 1047, CSA B64.4, UL, FM, and NSF/ANSI 372 standards.

Help Me Connect

This 8 inch Reduced Pressure Detector Assembly is designed for pipe systems using grooved connections. It features UL Classified and FM Approved outside stem and yoke (OSY) resilient seated gate valves for secure shutoff. The integral groove fittings allow for pipeline adjustment, ensuring a flexible and secure installation into your existing system.

View full details

Collapsible content

Additional Details

This 8 inch lead free reduced pressure detector backflow preventer assembly protects potable water systems by stopping the reverse flow of liquids due to backpressure or backsiphonage, especially where potential health hazards exist. It features an extremely compact design and is lighter than traditional models, approved for horizontal N pattern installation.

The assembly consists of a 304 stainless steel body with a quick-access sleeve, torsion spring check valves, outside stem and yoke (OSY) resilient seated gate valves, test cocks, and a corrosive-resistant bottom-mounted pressure relief valve. It includes a flood sensor with SentryPlus Alert® technology to detect excessive water discharges from the relief valve.

Flood Sensor & Connectivity

  • The integrated flood sensor with SentryPlus Alert® technology detects excessive water discharges from the relief valve.
  • When paired with an add-on sensor connection kit (sold separately), the sensor is activated to relay alerts for potential flooding events.
  • Connection kit options enable integration with Building Automation Systems (BAS) via RS-485 Modbus or the Nexa® platform through Wi-Fi, as well as cellular communication.
  • Note: An add-on connection kit is required to activate the flood sensor's communication features. Without it, the sensor is a passive component.

Features

  • Lead Free* construction ensures compliance with lead-free installation requirements.
  • Extremely compact design is 70% lighter than traditional models.
  • Durable 304 (Schedule 40) stainless steel housing & sleeve.
  • Groove fittings allow integral pipeline adjustment.
  • Patented torsion spring check provides the lowest pressure loss.
  • Unmatched ease of serviceability.
  • Replaceable check disc rubber.
  • UL Classified and FM Approved outside stem and yoke (OSY) resilient seated gate valves.
  • Bottom-mounted cast stainless steel relief valve.

Specifications

  • Product Type: Reduced Pressure Detector Assembly
  • Size: 8 inch
  • Construction: Lead Free
  • Installation Pattern: Horizontal N pattern
  • Housing & Sleeve Material: 304 (Schedule 40) stainless steel
  • Elastomers: EPDM, silicone, and Buna 'N'
  • Torsion Spring Checks Material: Noryl®, stainless steel
  • Check Discs Material: Reversible silicone or EPDM
  • Test Cocks Material: Lead Free* bronze body
  • Pins & Fasteners Material: 300 Series stainless steel
  • Springs Material: Stainless steel
  • Shutoff Valves: UL Classified and FM Approved OSY resilient seated gate valves
  • Flood Detection: SentryPlus Alert® flood sensor on relief valve

Performance Data

  • Temperature Range: 33°F - 110°F (0.5°C - 43°C)
  • Maximum Working Pressure: 175 PSI (12.1 bar)

Certificates & Approvals

  • ASSE 1047
  • CSA B64.4
  • UL Classified
  • FM Approved
  • NSF Certified to NSF/ANSI 372
  • AWWA C511-97

FAQs

What is the primary function of this 8 inch backflow preventer?

This backflow preventer is designed to protect potable water systems from contamination caused by backpressure or backsiphonage, ensuring water quality in health hazard applications.

What material is the housing made from?

The housing and sleeve are constructed from durable 304 (Schedule 40) stainless steel, offering corrosion resistance and longevity.

Does this assembly include a flood sensor?

Yes, it includes a SentryPlus Alert® flood sensor on the relief valve to detect excessive water discharges and help prevent flooding.

What installation orientation is this backflow preventer approved for?

This assembly is approved for horizontal N pattern installation, allowing for flexible setup in various piping configurations.

What is the maximum operating pressure for this unit?

The maximum working pressure for this 8 inch backflow preventer is 175 PSI (12.1 bar).